Plan Review Notes
Plan Review Notes For Project Z22090018
Project Number Z22090018
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2023-04-14 16:17:26PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -WATER METER BOX LOCATIONS ARE NOT ACCEPTABLE. DISTANCE
 TO WATER MAIN SHOULD BE MINIMIZED. REVISE LOCATIONS AND
 MAKE SURE MATCHES E22030048.
 -ADD ADDRESS TO LABEL OF EACH WATER METER.
 -BACKFLOW ASSEMBLY LOCATIONS WOULD NEED TO BE REVISED
 TO MINIMIZE DISTANCE TO NEW METER BOX LOCATIONS AND
 FOLLOW WPB STANDARDS.
 -REVISE CALLOUT THAT SAY 4??? FIRE METER AND DDCA.
 UTILITY DOES NOT TYPICALLY PROVIDE 4 INCH FIRE METERS.
 USUALLY PROVIDE DETECTOR METERS ON FIRELINE BACKFLOW
 ASSEMBLIES. ADD SIZE TO OTHER FIRELINE BACKFLOW
 ASSEMBLY.
 -WHEN REVISING ENGINEERING PLANS, ENSURE THERE ARE NOT
 TWO DETECTOR METERS AND FIRELINE BACKFLOW ASSEMBLIES ON
 ONE FIRELINE WATER SERVICE.
 -VERIFY PRIVATE FIRE SYSTEMS WILL NOT HAVE ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS.
 -CANNOT TELL IF THERE ARE ANY FIRELINES. IF THERE WILL
 BE FIRELINES, SHOW AND LABEL THEM ON PLANS ALONG FIRE
 FIRELINE BACKFLOW ASSEMBLY. ALSO SHOW AND LABEL FDC IF
 ANY ARE NEEDED OR REQUIRED.
 -WILL NEED TO UPDATE LANDSCAPING PLANS WITH REVISED
 UTILITY LOCATIONS AND UTILITIES AND TREES ARE SEPARATED
 WITH SUFFICIENT DISTANCE.
 -SHIFTING PROPERTY LINE IS NOT CALLED OUT ON
 ENGINEERING PLAN LIKE IT IS ON SITE PLAN. PLEASE ADD
 THAT CALLOUT.
 -SP-1 IS TITLED LANDSCAPE PLAN INSTEAD OF SITE PLAN.
 LANDSCAPE PLAN SEEMS TO BE LP-1. PLEASE UPDATE.
 -ON REVISED ENGINEERING PLANS, ENSURE THAT UTILITIES DO
 NOT INTERFERE WITH OPERATION OF DOORS.
 -A.101 WOULD NEED REVISION FOR CHANGING WATER METER AND
 BACKFLOW ASSEMBLY LOCATIONS.
 -RESPONSE LETTER SAID FDC WAS ADDED BUT CANNOT FIND ON
 ENGINEERING PLANS. SHOW AND LABEL ON SHEET C1.2
 -RESPONSE LETTER SAID WATER AND SEWER DEMAND
 CALCULATIONS WERE ADDED, BUT STILL CANNOT FIND. PLEASE
 ADD TO SHEET C1.2
 -ON ENGINEERING PLAN, SHOW THE UPDATED DOOR LOCATIONS.
 RESPECTFULLY,
 MARK HURLEY [email protected]