Plan Review Notes
Plan Review Notes For Project Z22090018
Project Number Z22090018
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-10-11 10:15:18PLEASE PROVIDE WRITTEN RESPONSES FOR THE FOLLOWING:
 -SHOW AND LABEL WATER METER BOX ON SHEET C1.1. SHOULD
 BE LOCATED OUTSIDE OF BUILDING AND PREFERABLY AWAY FROM
 PEDESTRIAN TRAFFIC.
 -SHOW AND LABEL BACKFLOW ASSEMBLIES ON SHEET C1.1.
 -SHOW AND LABEL PROPERTY LINE ON SHEET C1.1.
 -ADD WATER AND SEWER DEMAND CALCULATIONS ON SHEET C1.1.
 -IF FDC ARE NEEDED OR REQUIRED, THEN SHOW AND LABEL ON
 PLANS.
 -IS EXISTING BUILDING BEING DEMOLISHED AND NEW BUILDING
 BEING BUILT?
 -DOORS SHOULD NOT OPEN INTO RIGHT OF WAY. PLEASE UPDATE
 SITE PLAN.
 -COULD NOT LOCATE A LANDSCAPING PLAN IN SUBMITTAL
 PACKAGE. PLEASE ADD ONE WITH RESUBMITTAL.
 RESPECTFULLY,
 MARK HURLEY [email protected]