| Plan Review Notes For Project Z22090016 |
| Project Number |
Z22090016 |
|
| Review Stop |
PU |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-27 14:37:02 | -PLAN VIEW INCLUDING ROSEMARY AVENUE WOULD BE HELPFUL | | | TO DISCERN EXISTING CONDITIONS | | | -SEPARATE TAPS FOR WATER AND FIRE LINEWILL BE NECESSARY | | | PER DETAILS WS-1 AND WS-4 | | | -CLEANOUT NEEDED ADJACENT TO PROPERTY LINE FOR PROPOSED | | | SANITARY SEWER LATERAL SERVING GREASE TRAPS | | | -REMOVE EXISTING SANITARY SEWER LATERAL UP TO PROPERTY | | | LINE AND INSTALL CLEANOUT | | | -CCTV OF EXISTING SEWER MAIN IN ALLEY NECESSARY TO | | | DETERMINE IF THE MAIN WILL NEED TO BE LINED | | | -PROVIDE PROFILE FOR PROPOSED WATER AND SEWER SERVICE | | | LINES | | | -PREVIOUS COMMENT REGARDING INSTALLATION OF NEW WATER | | | MAIN BETWEEN SAPODILLA AND ROSEMARY NOT ADDRESSED | | | -NEED MORE INFORMATION ON TAPPING METHOD OF WATER MAIN | | | ON EVERNIA | | | -FIRE HYDRANT NEEDS ANCHOR TEE INSTALLED (8"X6") PER | | | DETAIL P-8 | | | | | | RICKY ELIZONDO [email protected] |
| |