| 2022-09-30 16:48:21 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -UTILITY BILLING SYSTEM AND HISTORIC PICTURES SHOW |
| | EXISTING LARGE DIAMETER DEDICATED FIRELINE AND DCDA |
| | NEAR SE AREA OF EXISTING BUILDING. SHOW AND LABEL WHAT |
| | IS HAPPENING TO THE EXISTING WATER SERVICE PIPE FROM |
| | WATER MAIN. |
| | -PROPOSED 8 INCH WM CANNOT BE PVC. WOULD HAVE TO BE |
| | DIP. |
| | -PAVEMENT RESTORATION LIMITS SHOULD EXTEND FURTHER WEST |
| | TO ENCOMPASS REMOVED WATER SERVICES. |
| | -ENTIRE FLAGS OF SIDEWALK WOULD NEED BE REPLACED WHERE |
| | METER BOXES ARE BEING REMOVED. SHOW ON ENGINEERING |
| | PLAN. |
| | -LABEL PARKING METERS ON ENGINEERING PLAN OR ADD THE |
| | SYMBOL TO LEGEND. |
| | -A PARKING METER MAY BE ENCROACHING IN FIRE HYDRANT |
| | CLEARANCE AREA. |
| | -SHOW EXISTING AND PROPOSED FDC. |
| | -SHOW PROPOSED POINT OF SERVICE VALVE FOR FIRELINE. |
| | -ENGINEERING PLAN SHOWS A LARGE UTILITY POLE IN NORTH |
| | DRIVEWAY. |
| | -LANDSCAPING SEEMS TO CONFLICT WITH PROPOSED UTILITIES |
| | IN TERMS OF LOCATION. SUBMIT ADDITIONAL LANDSCAPING |
| | PLAN SHEET SHOWING UTILITIES AND MAKE SURE THEY ARE |
| | APPROPRIATELY DISTANCED FROM EACH OTHER. |
| | -UPDATE SHEET LP3 TO DESCRIBE WHICH LOCATION IT IS. |
| | -WHAT IS HAPPENING TO THE LARGE EXISTING PALM TREE AT |
| | SOUTHEAST CORNER OF PROPERTY? |
| | -ON ENGINEERING PLAN, SHOW BOTH EDGE OF NORTHERN ALLEY |
| | PAVEMENT AND NORTHERN ALLEY RIGHT OF WAY LINE. |
| | -SHOW PAVEMENT RESTORATION IN ALLEY DUE TO UTILITY |
| | WORK. |
| | -IF THE EXISTING ONE STORY RESIDENCE BUILDING AND |
| | DUMPSTER AREA ARE BEING REMOVED, THEN ADD DEMO PLAN |
| | SHEET. |
| | -SHOW AND LABEL PROPOSED UTILITY EASEMENT FOR WATER |
| | METERS ON PRIVATE PROPERTY. |
| | -WATER METERS 3 INCH OR LARGER NEED TO BE INSTALLED |
| | ABOVE-GROUND. |
| | -ENGINEERING PLANS SHOWS MOSTLY CONCRETE ALONG EAST |
| | PROPERTY LINE, BUT LANDSCAPING PLANS SHOWS MOSTLY |
| | LANDSCAPING AREAS. |
| | -NORTHEAST DRIVEWAY IS MISSING DIRECTIONAL ARROWS ON |
| | MOST PLAN SETS. |
| | -VERIFY LOCATION OF DCDA. MAY BE CLOSER TO SIDEWALK |
| | THAN LABELED ON ENGINEERING PLAN. |
| | -WILL SIZE OF FIRELINE AND DCDA BE INCREASED? IF SO, |
| | NOTATE ON PLAN. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |