2023-04-05 07:09:55PLEASE PROVIDE WRITTEN RESPONSE TO THE FOLLOWING:
 -RESPONSE LETTER SAID WATER DEMAND CALCULATIONS, FDC,
 UTILITY EASEMENT, AND CLEANOUTS WERE ADDED, BUT CANNOT
 FIND IN ENGINEERING PLAN SET. ADD TO NEXT RESUBMITTAL.
 -RESPONSE LETTER SAID WATER SERVICE STANDARD DETAIL WS7
 AND WS5 WAS ADDED, BUT CANNOT FIND IN ENGINEERING PLAN
 SET. ADD TO NEXT RESUBMITTAL.
 -RESPONSE LETTER SAID ENGINEERING PLANS UPDATED TO SHOW
 SOUTHEAST DRIVEWAYS ARE BEING REMOVED. PLEASE SHOW THAT
 MORE CLEARLY ON DEMOLITION AND PGD PLAN SHEETS.
 -ADD WATER SERVICE STANDARD DETAIL WS2 TO ENGINEERING
 PLAN SET.
 -LANDSCAPING PLAN SHOWS CONFLICTS BETWEEN LANDSCAPING
 AND UTILITIES. IT DOES ALSO NOT SHOW UPDATED UTILITY
 LOCATIONS. IN RESUBMITTAL PACKAGE, PROVIDE COPY OF
 LANDSCAPING PLANS WITH UPDATED UTILITY LOCATIONS SHOWN.
 ENSURE THERE ARE NO CONFLICTS BETWEEN LANDSCAPING AND
 UTILITIES.
 -NOTIFY FIRE SYSTEM PLAN DESIGNER THAT FIRE SYSTEM NEAR
 FIRELINE BACKFLOW ASSEMBLY MUST COMPLY WITH WPB
 ENGINEERING WATER SERVICE STANDARD DETAIL WS5. THEY
 NEED TO INCLUDE COPY OF THAT DETAIL IN THEIR PLAN SET
 AND ENSURE NO GALVANIZED PIPE IS USED UPSTREAM OF
 FIRELINE BACKFLOW ASSEMBLY.
 -ARCHITECTURAL AND ENGINEERING PLANS SHOW A
 MICRO-MOBILITY STATION BUT LANDSCAPING PLANS DO NOT.
 PLEASE MAKE SURE ALL PLAN SETS ACCURATELY SHOW ANY
 MICRO-MOBILITY STATIONS.
 -ON SHEET C2.2, CALLOUT LOCATION OF FIRELINE BACKFLOW
 ASSEMBLY.