Plan Review Notes
Plan Review Notes For Project Z22090015
Project Number Z22090015
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2022-12-13 07:58:47PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 FOLLOWUP COMMENTS:
 4. SHOW AND LABEL EXISTING AND PROPOSED FIRE HYDRANTS
 ON WATER PLAN. RESPONSE: PLEASE REFER TO SHEET A301,
 THE LOCATION OF THE EXISTING FIRE HYDARNT WAS INCLUDED.
 NOT SATISIFED ??? INCLUDE UPDATE TO WATER PLAN (CIVIL
 SET) IN RESUBMITTAL.
 5. LARGE METER APPEARS TO BE PROPOSED IN MIDDLE OF
 WALKING PATH BLOCKING PEDESTRIAN TRAFFIC. COMPARE
 HARDSCAPE PLAN L300 TO SHEET C2.2. RESPONSE: WILL
 RESOLVE THIS ISSUE AFTER COORDINATION WITH LANDSCAPE
 ARCHITECT.
 NOT SATISIFED ??? RESOLVE IN RESUBMITTAL.
 8. LANDSCAPING AND UTILITIES APPEAR TO NOT HAVE
 SUFFICIENT SEPARATION DISTANCE. SUBMIT SEPARATE
 LANDSCAPING PLAN SHEET THAT SHOWS DISTANCE BETWEEN
 UTILITIES AND LANDSCAPING (TREES AND BUSHES). RESPONSE:
 NOT SATISIFIED ??? NO RESPONSE PROVIDED.
 9. SURVEY SHOWS OVERHEAD UTILITY LINE RUNNING ACROSS
 LOT 13. WHAT WILL HAPPEN TO OVERHEAD UTILITY LINE?
 RESPONSE: CURRENTLY CONFIRMING LOCATION.
 NOT SATISIFIED ??? REMINDER TO RESPOND IN RESUBMITTAL.
 11. SHOW EXISTING SEWER LATERAL FOR HISTORIC BUILDING
 ON WASTEWATER PLAN. RESPONSE: CURRENTLY CONFIRMING
 LOCATION.
 NOT SATISIFIED ??? INCLUDE UPDATE TO WASTEWATER PLAN IN
 RESUBMITTAL.
 13. DOMESTIC BACKFLOW ASSEMBLY IS EXCESSIVELY FAR FROM
 METER AND PROPERTY LINE. RELOCATE CLOSER TO METER AND
 PROPERTY LINE. RESPONSE: NOTED.
 NOT SATISIFIED ??? THIS REVIEW COMMENT NEEDS CORRECTIVE
 ACTION OTHER THAN JUST RECOGNITION.
 14. SAN MH1 HAS SW INV BUT APPEARS TO BE SE. RESPONSE:
 NOT SATISIFIED ??? NO RESPONSE PROVIDED.
 15. SHOW AND LABEL EXISTING AND PROPOSED CLEANOUTS ON
 C2.2. RESPONSE: NOTED.
 NOT SATISIFIED ??? THIS REVIEW COMMENT NEEDS CORRECTIVE
 ACTION OTHER THAN JUST RECOGNITION.
 16. WILL SEWER LATERAL AND PLUMBING PIPE WORK ALRIGHT
 WITH THE BASEMENT LEVELS? RESPONSE: MEP TO CONFIRM.
 NOT SATISIFIED ??? PROVIDE MEP CONFIRMATION IN
 RESUBMITTAL.
 18. ADD STANDARD DETAILS WS5 AND WS7 TO ENGINEERING
 PLAN SET. RESPONSE: NOTED.
 NOT SATISIFIED ??? WS5 AND WS7 NOT ADDED.
 19. ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET
 C2.2. RESPONSE: NOTED.
 NOT SATISFIED ??? WATER AND SEWER DEMAND WERE NOT
 ADDED.
 20. IF FDC ARE NEEDED OR REQUIRED, SHOW ON SHEET C2.2.
 RESPONSE: NOTED.
 NOT SATIFIED ??? FDC NOT SHOWN ON C2.2, BUT SEE FDC IN
 ARCHITECTURAL PLANS.
 21. SHOW AND LABEL ANY PROPOSED TRANSFORMER PADS.
 RESPONSE: CURRENTLY CONFIRMING LOCATION.
 NOT SATISIFIED ??? SHOW ON CIVIL PLAN RESUBMITTAL.
 23. THERE ARE LARGE UTILITY POLES AND OVERHEAD WIRES
 RUNNING ALONG NORTH PROPERTY LINE. HOW FAR IS BUILDING
 STRUCTURE SETBACK FROM THOSE? RESPONSE: CURRENTLY
 CONFIRMING LOCATION.
 NOT SATISIFIED ??? REMINDER TO INCLUDE IN RESUBMITTAL.
 24. SHOW AND LABEL REMOVAL OF EXISTING SOUTHEAST
 DRIVEWAYS. RESPONSE: NOTED.
 NOT SATISFIED ??? NOT SHOWN AND LABELED ON CIVIL PLANS.
 27. SHOW AND LABEL ANY PROPOSED UTILITY EASEMENTS. DID
 NOT SEE ONE FOR DOMESTIC WATER METER. RESPONSE: NOTED.
 WILL SHOW ONCE LOCATION IS CONFIRMED
 NEW REVIEW COMMENTS:
 -WPB GIS IS SHOWING EXISTING 6 INCH FIRELINE FOR 324
 DATURA ST. NEARBY PROPOSED FIRELINE ON SAME WATER MAIN.
 SHOW AND LABEL EXISTING FIRELINE ON WATER PLAN (CIVIL).
 -IS EXISTING 1 STORY BUILDING AT 321 DATURA (LOT 16)
 PROPOSED TO BE DEMOLISHED?
 -CALLOUT MINIMUM 18 INCH HORIZONTAL CLEARANCE DISTANCE
 BETWEEN SAN MH1 AND POTABLE PLUMBING PIPE.
 -L200 SHOWS TREE TOO CLOSE TO 3 INCH METERED WATER
 SERVICE. THERE ALSO APPEARS TO BE TREE ON TOP OF SAN
 MH1. IN ADDITION, THERE IS A TREE PROPOSED ON TOP OF
 PROPOSED FIRELINE WATER SERVICE. PLEASE PROVIDE
 HORIZONTAL CLEARANCE DISTANCE BETWEEN TREES AND
 UTILITIES.
 -VERIFY NO AUXILIARY WATER SOURCES SUCH AS WELLS WILL
 BE CONNECTED TO PRIVATE FIRE SYSTEM.
 -FIRE SYSTEM DESIGN INSIDE BUILDING MUST MEET
 REQUIREMENTS OF WPB PUBLIC UTILITIES AND ENGINEERING
 DEPARTMENTS. REFER TO SD WS5 AND CAN CONTACT
 [email protected] WITH ANY QUESTIONS.
 RESPECTFULLY,
 MARK HURLEY [email protected]