| 2022-12-13 07:58:47 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | FOLLOWUP COMMENTS: |
| | 4. SHOW AND LABEL EXISTING AND PROPOSED FIRE HYDRANTS |
| | ON WATER PLAN. RESPONSE: PLEASE REFER TO SHEET A301, |
| | THE LOCATION OF THE EXISTING FIRE HYDARNT WAS INCLUDED. |
| | NOT SATISIFED ??? INCLUDE UPDATE TO WATER PLAN (CIVIL |
| | SET) IN RESUBMITTAL. |
| | 5. LARGE METER APPEARS TO BE PROPOSED IN MIDDLE OF |
| | WALKING PATH BLOCKING PEDESTRIAN TRAFFIC. COMPARE |
| | HARDSCAPE PLAN L300 TO SHEET C2.2. RESPONSE: WILL |
| | RESOLVE THIS ISSUE AFTER COORDINATION WITH LANDSCAPE |
| | ARCHITECT. |
| | NOT SATISIFED ??? RESOLVE IN RESUBMITTAL. |
| | 8. LANDSCAPING AND UTILITIES APPEAR TO NOT HAVE |
| | SUFFICIENT SEPARATION DISTANCE. SUBMIT SEPARATE |
| | LANDSCAPING PLAN SHEET THAT SHOWS DISTANCE BETWEEN |
| | UTILITIES AND LANDSCAPING (TREES AND BUSHES). RESPONSE: |
| | NOT SATISIFIED ??? NO RESPONSE PROVIDED. |
| | 9. SURVEY SHOWS OVERHEAD UTILITY LINE RUNNING ACROSS |
| | LOT 13. WHAT WILL HAPPEN TO OVERHEAD UTILITY LINE? |
| | RESPONSE: CURRENTLY CONFIRMING LOCATION. |
| | NOT SATISIFIED ??? REMINDER TO RESPOND IN RESUBMITTAL. |
| | 11. SHOW EXISTING SEWER LATERAL FOR HISTORIC BUILDING |
| | ON WASTEWATER PLAN. RESPONSE: CURRENTLY CONFIRMING |
| | LOCATION. |
| | NOT SATISIFIED ??? INCLUDE UPDATE TO WASTEWATER PLAN IN |
| | RESUBMITTAL. |
| | 13. DOMESTIC BACKFLOW ASSEMBLY IS EXCESSIVELY FAR FROM |
| | METER AND PROPERTY LINE. RELOCATE CLOSER TO METER AND |
| | PROPERTY LINE. RESPONSE: NOTED. |
| | NOT SATISIFIED ??? THIS REVIEW COMMENT NEEDS CORRECTIVE |
| | ACTION OTHER THAN JUST RECOGNITION. |
| | 14. SAN MH1 HAS SW INV BUT APPEARS TO BE SE. RESPONSE: |
| | NOT SATISIFIED ??? NO RESPONSE PROVIDED. |
| | 15. SHOW AND LABEL EXISTING AND PROPOSED CLEANOUTS ON |
| | C2.2. RESPONSE: NOTED. |
| | NOT SATISIFIED ??? THIS REVIEW COMMENT NEEDS CORRECTIVE |
| | ACTION OTHER THAN JUST RECOGNITION. |
| | 16. WILL SEWER LATERAL AND PLUMBING PIPE WORK ALRIGHT |
| | WITH THE BASEMENT LEVELS? RESPONSE: MEP TO CONFIRM. |
| | NOT SATISIFIED ??? PROVIDE MEP CONFIRMATION IN |
| | RESUBMITTAL. |
| | 18. ADD STANDARD DETAILS WS5 AND WS7 TO ENGINEERING |
| | PLAN SET. RESPONSE: NOTED. |
| | NOT SATISIFIED ??? WS5 AND WS7 NOT ADDED. |
| | 19. ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET |
| | C2.2. RESPONSE: NOTED. |
| | NOT SATISFIED ??? WATER AND SEWER DEMAND WERE NOT |
| | ADDED. |
| | 20. IF FDC ARE NEEDED OR REQUIRED, SHOW ON SHEET C2.2. |
| | RESPONSE: NOTED. |
| | NOT SATIFIED ??? FDC NOT SHOWN ON C2.2, BUT SEE FDC IN |
| | ARCHITECTURAL PLANS. |
| | 21. SHOW AND LABEL ANY PROPOSED TRANSFORMER PADS. |
| | RESPONSE: CURRENTLY CONFIRMING LOCATION. |
| | NOT SATISIFIED ??? SHOW ON CIVIL PLAN RESUBMITTAL. |
| | 23. THERE ARE LARGE UTILITY POLES AND OVERHEAD WIRES |
| | RUNNING ALONG NORTH PROPERTY LINE. HOW FAR IS BUILDING |
| | STRUCTURE SETBACK FROM THOSE? RESPONSE: CURRENTLY |
| | CONFIRMING LOCATION. |
| | NOT SATISIFIED ??? REMINDER TO INCLUDE IN RESUBMITTAL. |
| | 24. SHOW AND LABEL REMOVAL OF EXISTING SOUTHEAST |
| | DRIVEWAYS. RESPONSE: NOTED. |
| | NOT SATISFIED ??? NOT SHOWN AND LABELED ON CIVIL PLANS. |
| | 27. SHOW AND LABEL ANY PROPOSED UTILITY EASEMENTS. DID |
| | NOT SEE ONE FOR DOMESTIC WATER METER. RESPONSE: NOTED. |
| | WILL SHOW ONCE LOCATION IS CONFIRMED |
| | NEW REVIEW COMMENTS: |
| | -WPB GIS IS SHOWING EXISTING 6 INCH FIRELINE FOR 324 |
| | DATURA ST. NEARBY PROPOSED FIRELINE ON SAME WATER MAIN. |
| | SHOW AND LABEL EXISTING FIRELINE ON WATER PLAN (CIVIL). |
| | -IS EXISTING 1 STORY BUILDING AT 321 DATURA (LOT 16) |
| | PROPOSED TO BE DEMOLISHED? |
| | -CALLOUT MINIMUM 18 INCH HORIZONTAL CLEARANCE DISTANCE |
| | BETWEEN SAN MH1 AND POTABLE PLUMBING PIPE. |
| | -L200 SHOWS TREE TOO CLOSE TO 3 INCH METERED WATER |
| | SERVICE. THERE ALSO APPEARS TO BE TREE ON TOP OF SAN |
| | MH1. IN ADDITION, THERE IS A TREE PROPOSED ON TOP OF |
| | PROPOSED FIRELINE WATER SERVICE. PLEASE PROVIDE |
| | HORIZONTAL CLEARANCE DISTANCE BETWEEN TREES AND |
| | UTILITIES. |
| | -VERIFY NO AUXILIARY WATER SOURCES SUCH AS WELLS WILL |
| | BE CONNECTED TO PRIVATE FIRE SYSTEM. |
| | -FIRE SYSTEM DESIGN INSIDE BUILDING MUST MEET |
| | REQUIREMENTS OF WPB PUBLIC UTILITIES AND ENGINEERING |
| | DEPARTMENTS. REFER TO SD WS5 AND CAN CONTACT |
| | [email protected] WITH ANY QUESTIONS. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |