Plan Review Notes
Plan Review Notes For Project Z22090015
Project Number Z22090015
Review Stop PU
Sequence Number 2
Notes
Date Text
2023-01-04 13:15:39-ADDRESS COMMENTS FROM LAST REVIEW NOTING EVIDENCE OF
 EXISTING MAIN THAT HAS A PROPOSED TAP
 -PLEASE READ THROUGH GIVEN CHECKLIST TO ADDRESS
 STANDARD COMMENTS THAT HAVE NOT BEEN FULFILLED, I.E.:
 -5 PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 -6 SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 -10 PROVIDE CCTV VIDEO AND PIPE RUN REPORT OF EXISTING
 GRAVITY INFRASTRUCTURES ALONG ENTIRE PROJECT FRONTAGE.
 (MANHOLE TO MANHOLE)
 -11 ADD NOTE TO PROVIDE 50 FT. PAVEMENT RESTORATION
 TRANSITION ON EACH SIDE OF PROPOSED TRENCH IN CITY
 MAINTAINED ROADWAY AREAS PER CITY OF WPB STANDARD
 DETAIL GC-8.
 -PROVIDE PROFILE AND VERTICAL CLEARANCES BETWEEN WATER,
 SEWER AND STORM LINES PER CITY OF WEST PALM BEACH
 STANDARD DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 SHOW EXISTING UNDERGROUND UTILITIES ON THE PROFILE TO
 EASILY DENOTE UTILITY CROSSINGS. THE PROFILE SHOULD
 SHOW PROPOSED PIPE FROM TIE-IN AT THE MAIN TO POINT OF
 SERVICE.
 -SHOW STATIONING AND HORIZONTAL SEPARATION CLEARANCE
 BETWEEN PROPOSED UTILITIES AND EXISTING UTILITIES
 AND/OR BASELINE.
 -LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 -SHOW EXISTING AND PROPOSED DEDICATED UTILITY EASEMENTS
 TO ALLOW ACCESS FOR CITY PERSONNEL TO PROPOSED UTILITY
 WATER METERS. VERIFY THAT THERE ARE NO STRUCTURES
 WITHIN EASEMENT.
 - SHOW DIRECTION OF FLOW ON PLAN VIEW FOR ALL SANITARY
 AND STORM SEWERS.
  
  
  
  
  
  