Plan Review Notes
Plan Review Notes For Project Z22090013
Project Number Z22090013
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-10-13 10:44:391. VARIANCE REQUEST FOR BUILDING FOOTPRINT LEVEL 6-7
 (MAX. 60%) PROPOSED 63%. PER SECTION 95-54(D.)(4.)
 UNAUTHORIZED VARIANCES. THE DAC IS NOT AUTHORIZED TO
 GRANT VARIANCES FOR ANY OF THE FOLLOWING: (E.) AN
 INCREASE IN MAXIMUM BUILDING FOOTPRINT ABOVE THE
 MAXIMUM FOOTPRINT ALLOWED BY THE URBAN REGULATIONS.
  
 2. WHAT IS THE TOTAL SQUARE FOOTAGE FOR OFFICE SPACE
 AND RETAIL? JUSTIFICATION LETTER STATES OFFICE AT
 425,798 SF; SHEET A0.01 STATES 378,137 SF; PLEASE
 CLARIFY SO STAFF MAY VERIFY PARKING REQUIREMENTS.
 RETAIL IN JUSTIFICATION LETTER IS 9,369 SF; SHEET A0.01
 STATES 9,161 SF. PARKING COUNT WILL HAVE TO BE ADJUSTED
 TO MEET RESPECTIVE REQUIREMENTS, THE RATIOS PER USE
 PROVIDED ON A0.01 ARE CORRECT.
  
 3. PLEASE PROVIDE DIMENSIONS OR CALLOUTS SPECIFYING
 DEPTH OF ALL SETBACKS ON SITE PLANS, FLOOR PLANS, AND
 ELEVATIONS. MINIMUM AND MAXIMUM SETBACKS SHOWN.
 A. CONDITIONAL SETBACK FOR PARKING USES ABOVE THE 5TH
 FLOOR; SHEET A1.06 ONLY SHOWS EVERNIA STREET SETBACK
 (PLEASE LABEL REQUIRED 27??? FROM BACK OF CURB)
 B. REQUIRED CONDITIONAL SETBACK ALONG FERN AND
 QUADRILLE PLAZA DR. IS 31??? (PLEASE LABEL ON SHEET
 A1.06 AND A1.07)
 C. PLEASE LABEL OR PROVIDE THE FEC ROW ABUTMENT
 SETBACKS AND CONDITIONAL SETBACKS ON SHEET A0.05 AND
 A1.01 ONWARD.
  
 4. SHEET A0.08 FAR
 A. LEVEL 1 FAR ??? FAR COUNT NEEDS TO INCLUDE STORAGE
 SPACE ADJACENT TO PARKING RAMP
 B. LEVEL 2 FAR ??? PORTION OF NORTHEAST STAIRWELL NOT
 SHOWN AS IT IS ON A1.02, PORTION NEEDS TO BE COUNTED IN
 FAR
 C. MINOR NOTE: SHEET A1.03 DOESN???T SHOW SOUTHERN
 ELEVATOR AS YELLOW SHADING FOR CIRCULATION
 D. LEVEL 4 FAR ??? PORTION OF NORTHWEST STAIRWELL NOT
 SHOWN AS IT IS ON A1.04, PORTION NEEDS TO BE COUNTED IN
 FAR
 E. PENTHOUSE FAR ??? ROOFTOP ON A1.26 SHOWS UNLABELED
 ROOM BELOW THE ELEVATOR OVERRUNS, PLEASE LABEL AND IF
 NOT MECHANICAL, SPACE WILL COUNT TOWARD FAR.
  
 5. PUBLIC OPEN SPACE REQUIREMENT NEEDS TO BE ADJUSTED.
 3% REQUIREMENT FOR LOTS 50,000-80,000SF; TOTAL REQUIRED
 2,292 SF. PLUS THE ADDITIONAL 3,501 SF FROM THE ALLEY
 ABANDONMENT 1:1 REPLACEMENT. TOTAL REQUIRED 5,793 SF.
 PLEASE ADJUST TABLE ON SHEET A0.06 OR LP-1 TO REFLECT
 CORRECT NUMBERS.
  
 6. WILL THE QUADRILLE PLAZA DRIVE RIGHT-OF-WAY BE A
 DEDICATED ROW? WHAT IS THE FINAL ROW WIDTH? PLEASE
 INDICATE ROW LINE ON PLANS, AS THIS IMPACTS SETBACKS
 AND SITE CONFIGURATION. PLEASE PROVIDE DETAILED
 DIMENSIONS AND CONDITIONS OF THE QUADRILLE PLAZA DR.
 EXTENSION (SIDEWALK, TRAVEL LANE, LANDSCAPE BUFFERS,
 PLANTERS/LANDSCAPE BEDS, ETC.) ON SITE AND GROUND FLOOR
 PLANS, AS IS SHOWN IN CIVIL PLANS.
  
 7. REMOVAL OF METERED ON-STREET PARKING WILL INCUR A
 REMOVAL FEE. PERMANENT REMOVAL FEE INCLUDED WITHIN
 RESOLUTION 191-22, $24,000 PER SPACE. PLEASE SPEAK WITH
 ED DAVIS ??? PARKING ADMINISTRATOR FOR ANY QUESTIONS
 REGARDING THE REMOVAL PROCESS OR FEES.
  
 8. PLEASE NOTE; IN THOSE CASES WHERE THE SIDE OF ANY
 PARKING STALL IS ADJACENT TO A WALL, FENCE, BUILDING,
 OR OTHER PHYSICAL OBSTRUCTION, THE STALL WIDTHS SHALL
 BE INCREASED BY A MINIMUM OF ONE FOOT. WHERE THERE IS
 AN OBSTRUCTION ON BOTH SIDES OF THE STALL, THE STALL
 WIDTHS SHALL BE INCREASED BY A MINIMUM OF TWO FEET.
  
 9. HISTORIC PRESERVATION ??? THE 501 FERN ST. BUILDING
 IS HISTORICALLY ELIGIBLE, PER THE REQUIREMENT OF SEC.
 94-131 THE BUILDING SHALL BE INTEGRATED INTO THE
 PROJECT AS PART OF THE NEW DEVELOPMENT. IF THE NEW
 QUADRILLE PLAZA DR. ROW DOES NOT CONSUME THIS BUILDING,
 BOTH HISTORIC PRESERVATION AND PLANNING STAFF REQUEST
 THAT THE DESIGN ELEMENTS FROM THE FRONT FA??ADE OF THE
 501 BUILDING BE PRESERVED, REPLICATED, OR INTEGRATED
 INTO THE GROUND-FLOOR DESIGN OF THE PROPOSED 515
 BUILDING AT THIS CORNER. PARTICULARLY THE FLUTED
 COLUMN-LIKE ELEMENTS AND THE HORIZONTAL STRIATIONS OF
 THE CORNICE AND ENTRY CANOPY.
  
 10. PLEASE LABEL AND PROVIDE SIDEWALK DIMENSIONS, AS
 WELL AS DIMENSIONS FOR PLANTERS/LANDSCAPE AREAS OR
 ELEMENTS WITHIN THE ROW ON BOTH THE GROUND FLOOR AND
 SITE PLAN A0.05 AND A1.01; APPEARS TO BE 8-12??? CLEAR,
 STAFF WOULD LIKE TO VERIFY THAT THE 8??? CLEAR PATH IS
 MAINTAINED. CIVIL PLANS PROVIDE THESE DIMENSIONS.
  
 11. SHEET A0.06D FOR THE FA??ADE ARTICULATION
 COMPLIANCE MATRIX: WEST, ON THE PROVIDED FENESTRATION
 IT IS NOTED THAT FA??ADE E, & G ARE MORE THAN 3 FT FROM
 THE LOT LINE; SHOULD THIS READ AS LESS THAN 3 FT?
  
 12. DUE TO THE SIGNIFICANCE IN SCALE FOR THE PROPOSED
 DEVELOPMENT PROJECT AND ITS IMPACT ON THE SURROUNDING
 ROADWAY NETWORK, STAFF REQUESTS THAT TDM STRATEGIES ARE
 DISCUSSED FOR THIS PROJECT.
  
 13. ON SHEET A0.06E, PLEASE PROVIDE PROJECTION
 DIMENSION ON THE HORIZONTAL FEATURES.
  
 14. QUADRILLE PLAZA DR. EXTENSION SHOULD BE RIGHT-TURN
 ONLY AT FERN ST. INTERSECTION, NOT ENOUGH QUEUING OR
 STACKING SPACE BEFORE THE TRAIN TRACKS.
  
 15. PLEASE ILLUSTRATE SITE VISIBILITY TRIANGLES SO THAT
 STAFF MAY VERIFY THAT THERE ARE NO OBSTRUCTIONS AT THE
 INTERSECTIONS AND DRIVES.
  
 16. MINOR NOTE: DRAWINGS ONLY PROVIDE ENTRY TO BIKE
 ROOM FROM OUTSIDE PLAZA, IS THIS INTENTIONAL?
  
 17. PLEASE PROVIDE A DETAILED AND DIMENSIONED SCHEMATIC
 FOR THE INTERNAL BIKE ROOM, SHOWING THE PROPOSED RACKS
 FROM A3.01 WITH ADEQUATE SPACING/SEPARATION WITHIN THE
 ROOM. PLEASE PROVIDE THE SPACING DETAILS FOR THE
 OUTSIDE BIKE RACKS AS WELL.
  
 18. PER SEC. 94-111; A MINIMUM OF ONE SHOWER AND
 CHANGING FACILITY SHALL BE PROVIDED TO BE AVAILABLE FOR
 ALL TENANTS AND SHALL BE LOCATED WITHIN THE BUILDING,
 OR WITHIN 200 FEET OF THE BUILDING ENTRANCE, FOR
 DEVELOPMENTS GREATER THAN 50,000 SQUARE FEET IN GROSS
 BUILDING AREA.
 PLEASE INDICATE ON THE PLANS WHERE THIS SHOWER FACILITY
 IS LOCATED.
  
 19. SHEET A3.01 PARKING STALL DIMENSIONS NOT COMPLIANT
 WITH CITY STANDARD AND STRIPING DETAIL. STANDARD SPACES
 SHOULD BE 8.5???X18??? AND ADA SPACES ARE 12X???18???
 WITH 5??? ADA AISLE. COMPACT SPACES ARE TYPICALLY
 8???X16???. PLEASE NOTE, ONLY 30% OF PARKING SPACES MAY
 BE DESIGNATED AS COMPACT SPACES AND SHALL BE INDICATED
 AS SUCH ON PLANS. PLEASE PROVIDE TOTAL CALCULATION.
 COMPACT SPACES WILL REQUIRE SEPARATE SIGNAGE
 DESIGNATING THESE SPACES AS COMPACT.
  
 20. SHEET A1.06 & A1.07 SHOWS WHAT APPEARS TO BE TANDEM
 SPACES, PLEASE NOTE PER SEC. 94-111 (E.): FOR
 COMMERCIAL USES, TANDEM PARKING SPACES SHALL BE COUNTED
 AS ONE SPACE UNLESS THERE IS A VALET ATTENDANT IN
 CHARGE OF THE OPERATION OF THE PARKING FACILITY DURING
 ALL OPERATING HOURS, AND SUCH REQUIREMENT IS
 ESTABLISHED THROUGH A RESTRICTIVE COVENANT. ALL
 RESTRICTIVE COVENANTS AND OTHER DOCUMENTS REQUIRED TO
 BE RECORDED SHALL BE ON CITY APPROVED FORMS, AND
 RECORDED IN THE PUBLIC RECORDS.
  
 ADDITIONALLY DUE TO THE INCLUSION OF STACKERS, PER SEC.
 94-111 (K.): MECHANICAL AND AUTOMATED PARKING. PARKING
 STRUCTURES WITH MECHANICAL PARKING SHALL PROVIDE A
 COMMERCIAL ATTENDANT DURING THE OPERATING HOURS OF THE
 FACILITY. SUCH OPERATION SHALL BE ENFORCED THROUGH A
 RESTRICTIVE COVENANT RECORDED IN THE PUBLIC RECORDS.
 ALL RESTRICTIVE COVENANTS AND OTHER DOCUMENTS REQUIRED
 TO BE RECORDED SHALL BE ON CITY APPROVED FORMS, AND
 RECORDED IN THE PUBLIC RECORDS.
  
 A VALET OR OPERATION ATTENDANT WILL BE REQUIRED FOR
 STACKERS, AS SUCH THE TANDEM SPACES IF SERVICED BY THE
 VALET OPERATIONS MAY COUNT AS 2 SPACES. PLEASE PROVIDE
 DETAILS OF THE STACKERS.
  
 21. PLEASE CLARIFY MIDDLE OF PARKING STRUCTURE ON SHEET
 A1.05, ELECTRIC SPACES APPEAR TO OVERLAP COMPACT
 SPACES, AND CONFLICT WITH THE PARKING RAMP.
  
 22. SHEET A1.01 SHOWS A CANOPY ON THE FERN ST. SIDE,
 PLEASE PROVIDE DETAILS THAT THE CANOPY IS IN COMPLIANCE
 WITH THE PROJECTION STANDARDS OF SEC. 94-109 TABLE
 IV-5. REQUIRES 10FT. VERTICAL CLEARANCE, MAXIMUM
 ENCROACHMENT IN ROW OF 12FT. AND MAXIMUM PROJECTION OF
 20FT.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426
  