Date Text
2023-01-13 19:32:22DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. THE SUBMITTED RESPONSE IS NOTED, HOWEVER
 THE CITY OF WEST PALM BEACH CODE OF ORDINANCES REQUIRES
 THAT ALL BUILDINGS AND ASSOCIATED EQUIPMENT HAVE A 24
 INCH FREEBOARD SO THAT THE CITY CAN MAINTAIN ITS
 COMMUNITY RATING SYSTEM (CRS) RATING WHICH GIVES WEST
 PALM BEACH PROPERTY OWNERS FLOOD INSURANCE DISCOUNTS
 THAT EXCEED MANY JURISDICTIONS. IF THE CITY DOES NOT
 ENFORCE THE PROVISION OF THE ORDINANCE AN AUDT BY FEMA
 WOULD RESULT IN INCREASED FLOOD INSURANCE RATES FOR ALL
 WEST PALM BEACH PROPERTY OWNERS. WE WILL NOT ALLOW THAT
 TO HAPPEN BECAUSE OF ANY ONE PROJECT. YOUR RESPONSE IS
 NOT CORRECT AND CANNOT BE THE FINAL RECORD. ACCORDING
 TO THE ADOPTED FLOOD INSURANCE RATE MAPS (FIRMS), THE
 PROPOSED BUILDING IS IN FLOOD ZONE AE, WITH A BASE
 FLOOD ELEVATION OF 13.4 FT NAVD. THE FIRST FLOOR OF THE
 BUILDING AND ALL ASSOCIATED MECHANICAL EQUIPMENT
 (CHILLERS, GENERATORS ETC.) SHALL BE 24 INCHES
 (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. GREASE/PETROLEUM INTERCEPTOR. A GREASE/PETROLEUM
 INTERCEPTOR WILL BE REQUIRED. FOR INFORMATION ON THE
 REQUIRED TYPE, SIZE AND LOCATION, PLEASE CONTACT RYAN
 BROWN, CHIEF PLUMBING INSPECTOR, DEVELOPMENT SERVICES
 DEPARTMENT, AT (561) 805-6692, OR BY EMAIL:
 [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  