| Plan Review Notes For Project Z22090007 |
| Project Number |
Z22090007 |
|
| Review Stop |
PU-CS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-13 07:17:10 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -CANNOT LOCATE EXISTING FIRELINE BACKFLOW ASSEMBLY ON | | | SITE WHERE SHOWN ON UTILITY PLAN. IF NONE ARE THERE, | | | THEN ONE WOULD NEED TO BE INSTALLED. LABEL ON PLAN. | | | -DOMESTIC METER CANNOT BE TAPPED OFF DEDICATED | | | FIRELINE. | | | -CALLOUT IS GOING OFF THE LEFT SIDE OF UTILITY PLAN AND | | | UNREADABLE. | | | -EXISTING 2 INCH DOMESTIC METER ON WEST SIDE OF | | | PROPERTY HARD TO ACCESS DUE TO BUSHES. ADD REMOVAL OF | | | BUSHES ENCROACHING WITHIN 18 INCHES OF METER BOX AND | | | BACKFLOW ASSEMBLY. | | | -VERIFY FIRE SYSTEM WILL NOT BE CONNECTED TO AN | | | AUXILIARY WATER SUPPLY SUCH AS A WELL. | | | -SHOW ALLEY PAVEMENT RESTORATION DUE TO UTILITY WORK. | | | -LABEL ADDRESS OF ADJACENT PROPERTY TO THE EAST ON | | | PLANS. THE ONE THAT HAS AN EASEMENT. | | | -COULD NOT LOCATE FIRELINE VALVE ON SITE. NOT SURE IF | | | BURIED UNDER LANDSCAPING AND BUSHES. | | | -IS EXISTING 8 INCH SEWER REMAINING AND DOES IT HAVE | | | ANY ADDITIONAL MANHOLE OR CLEANOUT AT ALLEY? | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |