| Date |
Text |
| 2022-09-02 11:40:23 | PLEASE PROVIDE WRITTEN RESPONSES THE FOLLOWING: |
| | -ADD LEGEND TO EACH ENGINEERING PLAN SHEET SHOWING |
| | SYMBOLS AND LINES USED THAT ARE NOT OTHERWISE LABELED. |
| | -SHOW UTILITY EASEMENTS ON SHEET C05. BACKFLOW |
| | ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENTS. |
| | -CALLOUT THE RP BACKFLOW ASSEMBLIES FOR THE PROPOSED 1 |
| | INCH METERED WATER SERVICES. ENSURE LABEL HAS SIZING. |
| | -SHOW AND LABEL SEWER LATERAL CLEANOUTS. |
| | -IS THE 2 INCH METER FOR IRRIGATION? IF NOT, IS A |
| | METERED IRRIGATION WATER SERVICE NEEDED? |
| | -ON DEMO PLAN SHOW AND EXISTING METERED WATER SERVICES |
| | AND LABEL WHAT IS HAPPENING TO THEM. |
| | -PROVIDE CLEARANCE DISTANCE BETWEEN SOUTHERN BUSH AND |
| | BACKFLOW ASSEMBLY SHOWN ON LANDSCAPING PLAN L2.0. |
| | -SHOW AND LABEL FDC ON PLANS IF ANY ARE NEEDED OR |
| | REQUIRED. |
| | -SHOW AND LABEL ALL EXISTING UTILITY POLES, LIGHT |
| | POLES, AND GUY WIRES NEAR PROPERTY ON ENGINEERING PLAN |
| | SHEETS IF THEY WILL REMAIN. |
| | -LABEL THE STREETS ON DEMO PLAN. |
| | -ONE OF THE STORMWATER LINES ON DIXIE SHOWS IT IN CLOSE |
| | PROXIMITY TO WATER MAIN. IS THAT CORRECT? |
| | -VERIFY THERE IS NO UTILITY OR FPL EASEMENTS RUNNING |
| | ALONG ALLEY. |
| | -ON AUTOTURN EXHIBIT, PLEASE SHOW UTILITY VAC TRUCK 7 |
| | FEET WIDE, 13 FEET HIGH, AND 36 FOOT LONG CAN |
| | SUCCESSFULLY NAVIGATE THROUGH PROPOSED ONE WAY ALLEY |
| | TURN. |
| | -IF THERE WILL BE ANY GREASE TRAPS OUTSIDE BUILDING, |
| | THEN SHOW AND LABEL ON PLANS. |
| | -MAY HAVE TO GRANT UTILITY EASEMENT FOR PROPOSED |
| | SANITARY SEWER MAIN. |
| | -LABEL ADJACENT PROPERTY ADDRESSES ON ENGINEERING PLAN |
| | SHEETS. |
| | -SHOW EXISTING SEWER LATERALS AND LABEL WHAT IS |
| | HAPPENING TO THEM. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| | |
| |