| Date |
Text |
| 2023-03-31 13:12:01 | DEMO SHEET | | | | | | -SHOW SECOND MANHOLE FROM SANITARY RUN | | | -CALL OUT EXISTING MAINS SIZES AND MATERIALS | | | -METER TO THE NORTH NOT SHOW | | | | | | WATER AND SEWER SHEET | | | | | | -PROVIDE 2ND VALVE FOR FIRELINE AT R/W LINE | | | -PROVIDE PROFILE FOR PROPOSED SEWER LATERAL TO ENSURE | | | CUT IN WILL NOT INTERFERE WITH EXISTING DRAINAGE | | | -PROVIDE PROFILES FOR FIRE LIE AND WATER SERVICE | | | -PROVIDE WATER SHUTDOWN PLAN FOR THE CUT IN TEE TO | | | ENSURE LEAST AMOUNT OF CUSTOMERS WILL BE OUT OF SERVICE | | | (IS A WET TAP NOT POSSIBLE?) | | | -CONDITION FOR SEWER MAIN NEEDS TO BE CHECKED TO SEE IF | | | PVC REPLACEMENT IS NECESSARY |
| |