Plan Review Notes
Plan Review Notes For Project Z22080024
Project Number Z22080024
Review Stop PU
Sequence Number 3
Notes
Date Text
2023-03-31 13:12:01DEMO SHEET
  
 -SHOW SECOND MANHOLE FROM SANITARY RUN
 -CALL OUT EXISTING MAINS SIZES AND MATERIALS
 -METER TO THE NORTH NOT SHOW
  
 WATER AND SEWER SHEET
  
 -PROVIDE 2ND VALVE FOR FIRELINE AT R/W LINE
 -PROVIDE PROFILE FOR PROPOSED SEWER LATERAL TO ENSURE
 CUT IN WILL NOT INTERFERE WITH EXISTING DRAINAGE
 -PROVIDE PROFILES FOR FIRE LIE AND WATER SERVICE
 -PROVIDE WATER SHUTDOWN PLAN FOR THE CUT IN TEE TO
 ENSURE LEAST AMOUNT OF CUSTOMERS WILL BE OUT OF SERVICE
 (IS A WET TAP NOT POSSIBLE?)
 -CONDITION FOR SEWER MAIN NEEDS TO BE CHECKED TO SEE IF
 PVC REPLACEMENT IS NECESSARY