Plan Review Notes
Plan Review Notes For Project Z22080024
Project Number Z22080024
Review Stop PU
Sequence Number 2
Notes
Date Text
2023-02-03 09:15:19-PREVIOUS COMMENT REGARDING CCTV NOT ADDRESSED
 -6" FIRELINE PROPOSED FOR REMOVAL IS SHOWN ON GIS AS A
 1" LATERAL SERVICE LINE. PLEASE VERIFY SIZE AMD
 MATERIAL. (WILL STILL NEED TO BE CUT AND CAP AT MAIN IF
 NOT USED)
 -A SECOND WATER SERVICE IS SHOWN ON GIS THAT IS NOT
 REFLECTED IN THE PLANS. PLEASE ACCOUNT FOR THIS SERVICE
 AND NOTE WHETHER IT WILL REMAIN OR NEED TO BE CUT AND
 CAP AT MAIN.
 -MANHOLE THAT LATERAL PROPOSED FOR REMOVAL IS CONNECTED
 TO WILL NEED TO BE REHABBED.
 -CLEANOUT NEAR PROPERTY LINE NEEDS TO BE NOTED AS POINT
 OF SERVICE. IF ON PRIVATE PROPERTY, AN EASEMENT WILL BE
 REQUIRED.
  