Plan Review Notes
Plan Review Notes For Project Z22080023
Project Number Z22080023
Review Stop PU-CS
Sequence Number 2
Notes
Date Text
2022-12-07 08:47:07PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -COULD NOT LOCATE WATER AND SEWER DEMAND CALCULATIONS
 ON UTILITY PLANS AS INDICATED IN RESPONSE LETTER.
 PLEASE ADD.
 -RESPONSE LETTER REFERRED TO SHEET C502, BUT COULD NOT
 FIND THAT SHEET IN CIVIL PLAN SET.
 -SHEET C503 SHOWS SYMBOLS THAT LOOK LIKE STREET SIGNS
 CLOSE TO WATER SERVICES. PLEASE ADD THOSE SYMBOLS TO
 THE LEGEND AND ENSURE AT LEAST SEVERAL FEET OF
 HORIZONTAL CLEARANCE DISTANCE BETWEEN POLES AND WATER
 SERVICES.
 -ON SHEET C200 CLEARLY LABEL WHAT IS HAPPENING TO
 EXISTING 7 FOOT UTILITY EASEMENT. IF REMAINING, SHOW
 CLEARLY ON UTILITY PLANS.
 -APPLICANT MUST PAY ALL UTILITY BILLING FEES RELATED TO
 PROJECT.
 -PROPOSED GREASE TRAP LOCATION ON SHEET C500 SEEMS
 UNUSUAL BECAUSE THERE IS NOT A NEARBY SANITARY SEWER
 MAIN OR LATERAL. NOT SURE IF PLUMBING PIPE IS EXISTING
 BUILDING AND THEN RETURNING OR THERE WILL BE LONG PIPE
 DISTANCE TO LATERAL.
 -PROPOSED 20 INCH WATER MAIN TAP MAY BE REVIEWED
 FURTHER AT ENGINEERING DEVELOPMENT SUBMITTAL.
 -THERE APPEARS TO BE LOCATION CONFLICTS WITH
 LANDSCAPING AND UTILITIES. PLEASE SHOW UTILITIES ON
 LANDSCAPING PLANS AND ENSURE THEY ARE APPROPRIATELY
 DISTANCED FROM EACH OTHER.
 -ADD STANDARD DETAIL P8 TO PLAN SET.
 -SEE NOTE 3 ON STANDARD DETAIL P8 AND REVISE FIRE
 HYDRANT LOCATIONS.
 -ENSURE LIGHTING ON PH1 AND WATER UTILITIES ARE
 APPROPRIATELY DISTANCED FROM EACH OTHER.
 -VERIFY NO AUXILIARY WATER SOURCES SUCH AS WELLS WILL
 BE CONNECTED TO PRIVATE FIRE SYSTEM.
 -T2.0 SHOWS DO NOT ENTER SIGNS ON SOUTHERN DRIVEWAY OF
 BARCELONA, BUT T2.1 SHOWS MOVING TRUCK ENTERING THE
 DRIVEWAY.
 RESPECTFULLY,
 MARK HURLEY [email protected]