| 2022-12-07 08:47:07 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -COULD NOT LOCATE WATER AND SEWER DEMAND CALCULATIONS |
| | ON UTILITY PLANS AS INDICATED IN RESPONSE LETTER. |
| | PLEASE ADD. |
| | -RESPONSE LETTER REFERRED TO SHEET C502, BUT COULD NOT |
| | FIND THAT SHEET IN CIVIL PLAN SET. |
| | -SHEET C503 SHOWS SYMBOLS THAT LOOK LIKE STREET SIGNS |
| | CLOSE TO WATER SERVICES. PLEASE ADD THOSE SYMBOLS TO |
| | THE LEGEND AND ENSURE AT LEAST SEVERAL FEET OF |
| | HORIZONTAL CLEARANCE DISTANCE BETWEEN POLES AND WATER |
| | SERVICES. |
| | -ON SHEET C200 CLEARLY LABEL WHAT IS HAPPENING TO |
| | EXISTING 7 FOOT UTILITY EASEMENT. IF REMAINING, SHOW |
| | CLEARLY ON UTILITY PLANS. |
| | -APPLICANT MUST PAY ALL UTILITY BILLING FEES RELATED TO |
| | PROJECT. |
| | -PROPOSED GREASE TRAP LOCATION ON SHEET C500 SEEMS |
| | UNUSUAL BECAUSE THERE IS NOT A NEARBY SANITARY SEWER |
| | MAIN OR LATERAL. NOT SURE IF PLUMBING PIPE IS EXISTING |
| | BUILDING AND THEN RETURNING OR THERE WILL BE LONG PIPE |
| | DISTANCE TO LATERAL. |
| | -PROPOSED 20 INCH WATER MAIN TAP MAY BE REVIEWED |
| | FURTHER AT ENGINEERING DEVELOPMENT SUBMITTAL. |
| | -THERE APPEARS TO BE LOCATION CONFLICTS WITH |
| | LANDSCAPING AND UTILITIES. PLEASE SHOW UTILITIES ON |
| | LANDSCAPING PLANS AND ENSURE THEY ARE APPROPRIATELY |
| | DISTANCED FROM EACH OTHER. |
| | -ADD STANDARD DETAIL P8 TO PLAN SET. |
| | -SEE NOTE 3 ON STANDARD DETAIL P8 AND REVISE FIRE |
| | HYDRANT LOCATIONS. |
| | -ENSURE LIGHTING ON PH1 AND WATER UTILITIES ARE |
| | APPROPRIATELY DISTANCED FROM EACH OTHER. |
| | -VERIFY NO AUXILIARY WATER SOURCES SUCH AS WELLS WILL |
| | BE CONNECTED TO PRIVATE FIRE SYSTEM. |
| | -T2.0 SHOWS DO NOT ENTER SIGNS ON SOUTHERN DRIVEWAY OF |
| | BARCELONA, BUT T2.1 SHOWS MOVING TRUCK ENTERING THE |
| | DRIVEWAY. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |