| 2022-09-04 08:41:43 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -ADD COVER SHEET TO CIVIL PLANS WITH MAP OF LOCATION. |
| | -ADD WATER AND SEWER DEMAND CALCULATIONS TO UTILITY |
| | PLAN SHEETS. |
| | -FOR CIVIL PLAN SET, ADD STANDARD DETAILS SHEET WITH |
| | REFERENCED STANDARD DETAILS. |
| | -DIXIE HWY IS FDOT ROW. |
| | -ADD WORDING ABOVE-GROUND TO THE LABELS OF THE PROPOSED |
| | 6 INCH AND 4 INCH METERS. |
| | -SURVEY IS NOT SIGNED, SEALED, AND DATED. |
| | -SURVEY SHOWS EXISTING UTILITY EASEMENTS RUNNING |
| | THROUGH PROPERTY, BUT THEY ARE NOT SHOWN AND LABELED ON |
| | CIVIL PLANS. |
| | -STRUCTURES MAY NOT BE BUILT ON UTILITY EASEMENTS |
| | WITHOUT APPROVAL OF CITY. |
| | -CIVIL PLANS SHOW CONFLICTS WITH UTILITY POLES AND GUY |
| | WIRES. ADD DEMO PLAN SHEET IF THOSE ARE BEING REMOVED, |
| | RELOCATED, OR UNDERGROUNDED. |
| | -SHOW AND LABEL ANY PROPOSED TRANSFORMER PADS. |
| | -JUSTIFICATION DOCUMENT SAID THERE ARE PROPOSED |
| | RESTAURANTS, BUT DID NOT SEE ANY GREASE TRAPS. SHOW AND |
| | LABEL ANY GREASE TRAPS WHICH ARE PROPOSED OUTSIDE OF |
| | BUILDING. |
| | -PROPOSED TAPS ON 20 INCH WATER MAIN WOULD REQUIRE |
| | APPROVAL OF MICHAEL TECHNOW. |
| | -SHEET C501. UTILITY OR LIGHT POLES APPEAR TO BE CLOSE |
| | TO WATER UTILITIES. PROVIDE AT LEAST SEVERAL FEET OF |
| | HORIZONTAL CLEARANCE DISTANCE BETWEEN THEM. |
| | -ADD A LANDSCAPING SHEET SHOWING ALL TREES, BUSHES, AND |
| | UTILITIES. ENSURE THERE IS ADEQUATE CLEARANCE DISTANCE |
| | BETWEEN PLANTS AND UTILITIES. |
| | -ON LANDSCAPING, CIVIL, AND ARCHITECTURAL PLANS, ADD |
| | LEGEND IDENTIFYING SYMBOLS USED. |
| | -THE SOUTHERN BUILDING SHOWS SOMETHING THAT LOOKS LIKE |
| | OUTDOOR TABLES ADJACENT THE NORTH SIDE. CIVIL PLANS |
| | SHOW ABOVE-GROUND WATER METER, TRAFFIC SIGN, AND LIGHT |
| | POLE THERE ALSO. WILL THERE BE ADEQUATE WIDTH FOR |
| | PEDESTRIAN MOVEMENT THERE? |
| | -BYPASS OF 6 INCH WATER METER FOR SOUTHERN BUILDING |
| | CANNOT BE IN OR UNDER CURB. |
| | -WHAT IS THE PLAN FOR THE AREA BETWEEN THE BULBOUTS? |
| | ARE THEY PARKING SPOTS? SHOW OR DETAIL MORE CLEARLY ON |
| | PLANS. |
| | -SHOW TRAFFIC SIGN NEAR NORTHEAST CORNER OF SOUTHERN |
| | BUILDING ON UTILITY PLANS. CALLOUT MINIMUM 18 INCH |
| | CLEARANCE DISTANCE BETWEEN SIGN AND BACKFLOW ASSEMBLY. |
| | ALSO WILL TRAFFIC SIGN CONFLICT WITH TRAFFIC GATE |
| | OPENING? |
| | -IS THE DRIVE PATH ON THE EAST SIDE OF SOUTHERN |
| | BUILDING ONE WAY? SHOW OR DETAIL MORE CLEARLY ON PLANS. |
| | ALSO THE NORTHEAST CURB ISLAND DOES NOT ALIGN WITH IT. |
| | -PAVEMENT RESTORATION LIMITS FROM UTILITY WORK ARE |
| | LIKELY MUCH LARGER THAN SHOWN ON CIVIL PLANS. |
| | -LIGHT POLE SHOWING IN DRIVEWAY ON SHEET C501. |
| | -BACKFLOW ASSEMBLIES FOR NORTH BUILDING MAY BE |
| | CONFLICTING WITH A WALL. CALLOUT THE OBJECT AND RESOLVE |
| | ANY LOCATION CONFLICTS. |
| | -ATTEMPT TO REPOSITION THE WATER SERVICES FOR THE NORTH |
| | BUILDING SUCH THAT THE FIRE SERVICE DOES NOT RUN |
| | UNDERNEATH TWO OTHER LARGE WATER SERVICES. |
| | -WATER METER BOXES MAY NOT ENCROACH INTO CURBS. WATER |
| | VALVE BOXES SHOULD ALSO NOT BE LOCATED IN CURBS. |
| | -C500. PROPOSED BACKFLOW ASSEMBLIES CONFLICTING WITH |
| | EXISTING STORM MANHOLE AND CLEANOUT AS SHOWN ON SURVEY. |
| | -PLANS DO NOT SHOW ANY OF THE EXISTING NORTH SOUTH OR |
| | EAST WEST CROSSWALKS. |
| | -APPLICANT MAY BE REQUIRED TO REROUTE OR BUILD NEW |
| | WATER MAIN FOR THE ONE THAT IS PROPOSED FOR REMOVAL. |
| | -ADD ADJACENT PROPERTY ADDRESSES ON CIVIL PLANS. |
| | -SHOW AND LABEL FDC IF THEY ARE NEEDED OR REQUIRED. |
| | ENSURE THEY ARE ACCEPTABLE DISTANCE FROM FIRE HYDRANT. |
| | RESPECTFULLY, |
| | MARK HURLEY [email protected] |
| |