| Plan Review Notes For Project Z22080016 |
| Project Number |
Z22080016 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-13 10:56:22 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -PROPOSED METER AND BACKFLOW LOCATION ARE NOT | | | SATISFACTORY. SEE RESPONSE LETTER WITH PRIOR COMMENTS | | | FOR GUIDANCE. | | | -ON ENGINEERING PLAN, SHOW GUY WIRE ANCHORS FOR UTILITY | | | POLE NEAR THE FIRE HYDRANT. | | | -AT LEAST TWO METERED WATER SERVICES FOR THE BUILDINGS | | | TO BE DEMOLISHED ARE NOT SHOWN AND LABELED ON PLANS. | | | SHOW AND LABEL. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |
Print |
|