Plan Review Notes
Plan Review Notes For Project Z22080012
Project Number Z22080012
Review Stop STORM
Sequence Number 3
Notes
Date Text
2023-03-15 11:39:47THE CIVIL PLANS EMAILED TO T. WARD ON 3/14/23 ARE
 SUFFICIENT FOR SITE PLAN APPROVAL WITH THE FOLLOWING
 DEFICIENCIES IDENTIFIED. THESE CAN BE ADDRESSED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 1. EXISTING UTILITIES ARE MISSING FROM THE RIGHT OF WAY
 ON SHEET C-5.
  
 2. RUNOFF IN THE EXFILTRATION TRENCH SYSTEM TO PASS
 OVER A WEIR BEFORE FLOWING THROUGH A BLEEDER.
  
 3. SUGGEST EXTENDING SIDEWALK BEHIND THE PARKWAY ON 3RD
 ST. TO THE EAST SIDE OF THE EAST DRIVEWAY TO 3RD ST.
 THIS WILL SHORTEN THE LANDSCAPE AREA ALONG THE EAST
 PROPERTY LINE.
  
 4. REMOVE OR MOVE THE DRAINAGE OUTFALL PIPE LABEL NECT
 TO STRUCTURE NO. 11.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]