2023-03-15 13:17:58CONDITIONS OF APPROVAL (WILL BE REQUIRED TO ADDRESS
 DURING ENGINEERING REVIEW)
  
 PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 CONDITIONS FOR WATER AND SEWER
 ALL INSTALLED WATER MAIN MUST BE DIP PER CITY
 STANDARDS
 DOUBLE VALVING AND JUMPER ASSEMBLY WILL BE NECESSARY
 FOR TIE-INS TO EXISTING WATER MAIN FOR PIGGING AND
 FLUSHING TESTING PER CITY DETAIL P-6
 LABEL ALL FITTING THAT ARE TO BE INSTALLED
 INCLUDE ALL DRY UTILITIES ON THE PLANS, INCLUDING THOSE
 PROPOSED FOR INSTALLATION
 PROFILE 4 SHOWS PROPOSED WATER MAIN TO ONLY BE 9.5
 INCHES ABOVE EXISTING 30" SEWER MAIN
 HAVE AN EMERGENCY PREPAREDNESS PLAN IN THE EVENT OF THE
 30" SEWER MAIN COLLAPSING DURING CONSTRUCTION
  
 MORE COMMENTS PENDING REVISIONS ON NEXT SUBMITTAL
  