2022-10-24 14:04:13PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -C900 CANNOT BE USED FOR THE WATER MAINS AND LARGE
 WATER SERVICES. SWITCH TO DIP.
 -ADJUST BOUNDARIES OF PROPOSED UTILITY EASEMENTS SO
 THEY DO NOT INCLUDE THE DCDA FIRELINE BACKFLOW
 ASSEMBLIES.
 -4 INCH WATERMETER SHOULD HAVE 4 INCH PIPE FROM METER
 TO WATER MAIN.
 -6 INCH WATER METER SHOULD HAVE 6 INCH PIPE AND
 FITTINGS INSTEAD OF 4 INCH.
 -ADD PROFILE OF ENTIRE PROPOSE WATER MAIN WITH
 SUBMITTAL PACKAGE AT ENGINEERING DEVELOPMENT SUBMITTAL.
 -LANDSCAPE PLAN SEEMS TO SHOW TREES IN THE MIDDLE OF
 SIDEWALK AT THE SOUTHWEST AREA OF 4TH ST. IS THAT
 INTENTIONAL AND WILL IT IMPEDE PEDESTRIAN OR ADA
 MOVEMENT?
 -ALSO ON LANDSCAPE PLAN DISTANCE BETWEEN TREE TRUNK AND
 SEWER CLEANOUT NEAR THE NORTHWEST SIDE LOOKS TOO CLOSE.
 IF UNDER 5 FEET NEED MORE HORIZTONAL CLEARANCE
 DISTANCE.
 RESPECTFULLY,