| Plan Review Notes For Project Z22080012 |
| Project Number |
Z22080012 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-24 14:04:13 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -C900 CANNOT BE USED FOR THE WATER MAINS AND LARGE | | | WATER SERVICES. SWITCH TO DIP. | | | -ADJUST BOUNDARIES OF PROPOSED UTILITY EASEMENTS SO | | | THEY DO NOT INCLUDE THE DCDA FIRELINE BACKFLOW | | | ASSEMBLIES. | | | -4 INCH WATERMETER SHOULD HAVE 4 INCH PIPE FROM METER | | | TO WATER MAIN. | | | -6 INCH WATER METER SHOULD HAVE 6 INCH PIPE AND | | | FITTINGS INSTEAD OF 4 INCH. | | | -ADD PROFILE OF ENTIRE PROPOSE WATER MAIN WITH | | | SUBMITTAL PACKAGE AT ENGINEERING DEVELOPMENT SUBMITTAL. | | | -LANDSCAPE PLAN SEEMS TO SHOW TREES IN THE MIDDLE OF | | | SIDEWALK AT THE SOUTHWEST AREA OF 4TH ST. IS THAT | | | INTENTIONAL AND WILL IT IMPEDE PEDESTRIAN OR ADA | | | MOVEMENT? | | | -ALSO ON LANDSCAPE PLAN DISTANCE BETWEEN TREE TRUNK AND | | | SEWER CLEANOUT NEAR THE NORTHWEST SIDE LOOKS TOO CLOSE. | | | IF UNDER 5 FEET NEED MORE HORIZTONAL CLEARANCE | | | DISTANCE. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |