Notes
Date Text
2023-01-24 10:21:44-MANHOLES WITH LATERALS BEING CORED INTO THEM WILL
 REQUIRE REHABBING
 -DENOTE ANY AND ALL WATER SERVICES THAT ARE TO BE
 REMOVED AND CAPPED AT MAIN
 -PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 CONDITIONS FOR WATER AND SEWER
 -ALL INSTALLED WATER MAIN MUST BE DIP PER CITY
 STANDARDS
 -DOUBLE VALVING AND JUMPER ASSEMBLY WILL BE NECESSARY
 FOR TIE-INS TO EXISTING WATER MAIN FOR PIGGING AND
 FLUSHING TESTING PER CITY DETAIL P-6
 -LABEL ALL FITTING THAT ARE TO BE INSTALLED
 -INCLUDE ALL DRY UTILITIES ON THE PLANS, INCLUDING
 THOSE PROPOSED FOR INSTALLATION
 -PROFILE 4 SHOWS PROPOSED WATER MAIN TO ONLY BE 9.5
 INCHES ABOVE EXISTING 30" SEWER MAIN
 -HAVE AN EMERGENCY PREPAREDNESS PLAN IN THE EVENT OF
 THE 30" SEWER MAIN COLLAPSING DURING CONSTRUCTION
  