Notes
Date Text
2022-09-07 16:55:54-CALL FOR MANHOLE TO BE INSTALLED AT JUNCTION OF
 PROPOSSED SANITARY LATERAL AND 30" GRAVITY MAIN PER
 HEALTH DEPT STANDARDS.
 -UPSIZE THE EXISITNG 8" WM ON ROSEMARY TO 12" WITHIN
 PROJECT LIMITS (3RD ST TO 5TH ST).
 -UPSIZE THE EXISTING 8" WM ON W RAILROAD AVE TO 10"
 WITHIN PROJECT LIMIT. (3RD ST. TO 5TH ST.)
 -FOR ENG SUBMITTAL PROVIDE LOS CALCULATIONS AND FIRE
 FLOW CALCS ON PLAN SHEET.
  