Plan Review Notes
Plan Review Notes For Project Z22070023
Project Number Z22070023
Review Stop STORM
Sequence Number 2
Notes
Date Text
2023-05-06 14:48:52THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3-28-2023 SUBMITTAL:
  
 1. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE VERTICAL
 DATUM CONVERSION TO NGVD1929 ON THE SURVEY.
  
 2. [PARTIALLY SATISFIED - RECESSED DOORS NOT SHOWN ON
 THE ENGINEERING PLANS.] ENGINEERING PLAN AND LANDSCAPE
 PLAN DO NOT MATCH ARCHITECTURAL SITE PLAN.
  
 3. [SATISFIED] 24 FEET NEEDED AS BACKUP SPACE FOR
 90-DEGREE PARKING.
  
 4. [SATISFIED] ENGINEERING PLAN SHOWS DOORS OPENING AT
 BOTTOM OF EXTERIOR STAIRS.
  
 5. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS
 AND COORDINATE PLANTINGS WITH THE UTILITIES.
  
 6. [NOT SATISFIED - NOT FOUND ON SHEET C2.1] PROVIDE A
 CONTROL STRUCTURE DETAIL.
  
 7. [NOT SATISFIED - NOT FOUND ON SHEET C1.1] PROVIDE
 CROSS SECTIONS FROM CENTERLINE OF RIGHTS OF WAY TO THE
 BUILDING FACES. SHOW AND LABEL SURFACE FEATURES, GRADE
 BREAKS, GENERAL SURFACE SLOPES, FINISHED FLOOR
 ELEVATION, RIGHT OF WAY LINES WITH THE STREET
 IDENTIFIED, DIMENSIONS FROM RIGHT OF WAY TO SURFACE
 FEATURES.
  
 8. [SATISFIED] IDENTIFY THE GREEN DASHED LINE RUNNING
 NORTH-SOUTH BETWEEN THE GREASE TRAPS AND DRAINAGE
 SYSTEM ON SHEET C1.1.
  
 9. [NOT SATISFIED] SHOW MILL AND RESURFACE LIMITS.
  
 10. [PARTIALLY SATISFIED] CALLOUT WHERE NEW OR
 REPLACEMENT SIDEWALK WILL BE CONSTRUCTED AS PART OF
 THIS PROJECT. ADDITIONAL COMMENT: DRIVEWAY FOR THIS
 DEVELOPMENT IS NOT IN THE SAME LOCATION AS THE PROPOSED
 PARKING LOT THAT IS SHOWN ON THE STREETSCAPE PLANS. THE
 6-INCH THICK SIDEWALK ACROSS THE DRIVEWAY WILL NOT LINE
 UP WITH THIS DEVELOPMENT.
  
 NEW COMMENTS (3-28-2023 SUBMITTAL):
  
 11. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH
 EXFILTRATION TRENCH SYSTEMS.
  
 12. REMOVE THE LARGE BLACK ARROW ON NORTH SIDE OF
 BUILDING ON SHEET C1.1.
  
 13. WEST INVERT MISSING FOR STRUCTURE CS-2.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  