2022-08-08 18:59:56PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ARCHITECTURAL DRAWINGS DO NOT MATCH SITE PLAN LAYOUT
 WITH REGARD TO PARKING LOT AREA. PLEASE ENSURE PLANS
 HAVE SAME GENERAL LAYOUT.
 -BACKFLOW ASSEMBLIES ON ENGINEERING PLAN APPEAR TO
 CONFLICT WITH PLANTS ON LANDSCAPING PLAN. ARCHITECTURAL
 PERSPECTIVE 3 ALSO SHOWS LARGE BUILDING OPENING ON
 NORTH SIDE OF BACKFLOW ASSEMBLIES.
 -WHY ARE GREASE TRAPS PROPOSED?
 -PLANS PROPOSE A SHARED SEWER LATERAL BETWEEN
 NEIGHBORING PROPERTIES. EACH PROPERTY MAY BE ADVERSELY
 AFFECTED BY ACTIONS OF THE OTHER PROPERTY OWNERS. THE
 SIZING IS ALSO LESS THAN WOULD HAVE WITH SEPARATE SEWER
 LATERALS.
 -IF FDC ARE NEEDED OR REQUIRED, THEN SHOW AND LABEL ON
 PLANS.
 -ON ENGINEERING PLAN, LABEL PROPERTY LINES OF 818 N
 RAILROAD AS WELL AS THE PROPERTY TO THE SOUTH ACROSS
 THE ALLEY.
 -CALLOUT MINIMUM CLEARANCE DISTANCE BETWEEN END OF
 PROPOSED WATER MAIN AND EXISTING SANITARY SEWER
 MANHOLE.
 -RECENT PICTURES OF AREA SHOW UTILITY POLES AND GUY
 WIRES NEAR SOUTH SIDE OF ALLEY.
 RESPECTFULLY,