| Notes |
| Date |
Text |
| 2022-08-08 18:59:56 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -ARCHITECTURAL DRAWINGS DO NOT MATCH SITE PLAN LAYOUT | | | WITH REGARD TO PARKING LOT AREA. PLEASE ENSURE PLANS | | | HAVE SAME GENERAL LAYOUT. | | | -BACKFLOW ASSEMBLIES ON ENGINEERING PLAN APPEAR TO | | | CONFLICT WITH PLANTS ON LANDSCAPING PLAN. ARCHITECTURAL | | | PERSPECTIVE 3 ALSO SHOWS LARGE BUILDING OPENING ON | | | NORTH SIDE OF BACKFLOW ASSEMBLIES. | | | -WHY ARE GREASE TRAPS PROPOSED? | | | -PLANS PROPOSE A SHARED SEWER LATERAL BETWEEN | | | NEIGHBORING PROPERTIES. EACH PROPERTY MAY BE ADVERSELY | | | AFFECTED BY ACTIONS OF THE OTHER PROPERTY OWNERS. THE | | | SIZING IS ALSO LESS THAN WOULD HAVE WITH SEPARATE SEWER | | | LATERALS. | | | -IF FDC ARE NEEDED OR REQUIRED, THEN SHOW AND LABEL ON | | | PLANS. | | | -ON ENGINEERING PLAN, LABEL PROPERTY LINES OF 818 N | | | RAILROAD AS WELL AS THE PROPERTY TO THE SOUTH ACROSS | | | THE ALLEY. | | | -CALLOUT MINIMUM CLEARANCE DISTANCE BETWEEN END OF | | | PROPOSED WATER MAIN AND EXISTING SANITARY SEWER | | | MANHOLE. | | | -RECENT PICTURES OF AREA SHOW UTILITY POLES AND GUY | | | WIRES NEAR SOUTH SIDE OF ALLEY. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] | | | |
| |