Plan Review Notes
Plan Review Notes For Project Z22070022
Project Number Z22070022
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-08-10 13:30:29PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ENSURE FDC IS ACCEPTABLE DISTANCE FROM CITY FIRE
 HYDRANT.
 -CLEARLY SHOW AND LABEL PROPERTY LINES ON PLANS.
 -RECENT PICTURES SHOW CHAIN LINK FENCE AROUND PARTS OF
 THE PROPERTY. WILL IT REMAIN?
 -THERE APPEARS TO BE A PRIVATE FIRE HYDRANT NEAR
 SOUTHEAST AREA OF PROPERTY. PLEASE LABEL IT ON
 ENGINEERING PLAN.
 -ON SHEET C1.1 LABEL THE UTILITY RUNNING UNDER THE BIKE
 RACK AND NEAR THE CROSSWALK.
 -SHOW UTILITIES ON LANDSCAPE PLAN AND ENSURE NO
 CONFLICTS BETWEEN TREES AND UTILITIES.
 -CALLOUT MINIMUM HORIZONTAL CLEARANCE DISTANCE BETWEEN
 END OF WATER MAIN AND SEWER MANHOLE IN ALLEY.
 -CURRENTLY THERE ARE UTILITY POLES AND OVERHEAD
 UTILITIES ALONG NORTH SIDE OF BUILDING. THEY MAY
 CONFLICT WITH PROPOSED IMPROVEMENTS.
 -ADD SEWER LATERAL CLEANOUT ADJACENT PROPERTY LINE.
 -SITE PLAN SHOWS DUMPSTER DETAIL, BUT DOES NOT SHOW
 LOCATION ON PLAN.
 -ARCHITECTURAL PERSPECTIVE 1 SHOWS LARGE NORA MONUMENT
 SIGN, BUT IT IS NOT SHOWN AND LABELED ON PLAN SETS.
 -ON LANDSCAPE PLAN, CLEARLY SHOW AREAS OF LANDSCAPE AND
 HARDSCAPE.
 RESPECTFULLY,
 MARK HURLEY
 [email protected]