| Project Number |
Z22070019 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-06 11:12:39 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -DOMESTIC BACKFLOW ASSEMBLY SHOULD NOT BE IN THE | | | SIDEWALK AND SHOULD BE ON PRIVATE PROPERTY. RELOCATE | | | SOUTH JUST PAST THE PROPERTY LINE. ENSURE COORDINATE | | | WITH LANDSCAPING PLAN AS THERE MAY BE BUSH NEARBY. | | | -ADD GRAPHIC SCALE / VISUAL MEASUREMENT ICON TO CIVIL | | | PLAN SHEET C204. | | | -DID NOT SEE FDC ON PLANS. SHOW AND LABEL IF ONE IS | | | NEEDED OR REQUIRED. | | | -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED | | | CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS. | | | -SHOW AND LABEL ANY PROPOSED GREASE TRAPS OR | | | TRANSFORMER PADS IF THEY ARE OUTSIDE BUILDING. | | | -WILL IRRIGATION WATER BE FED BY THE DOMESTIC METERED | | | WATER SERVICE? | | | -ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET C204. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |