Plan Review Notes
Plan Review Notes For Project Z22070019
Project Number Z22070019
Review Stop PU
Sequence Number 2
Notes
Date Text
2023-07-13 12:28:48-PROVIDE DEMOLITION/EXISTING CONDITIONS PLAN SHEET
 -SHOW ALL EXISTING LATERALS/SERVICES ALONG AMIN
 FRONTING PROJECT BOUNDARY
 -SHOW ALL EXISTING AND PROPOSED VALVES AND
 APPURTENANCES LEGIBLY
 -SPECIFY MEANS OF CONNECTION TO SEWER
 -4" TAPS PROPOSED WHEN EXISTING MAIN IS 6"
 -REFER TO WS STANDARD DETAILS FOR PROPER LOCZTION OF
 METER INSTALLATION
 -DENOTE SERVICES AS PRIVATE, AS APPLICABLE
 -ALL LATERALS/SERVICES NOT TO BE USED MUST BE CUT AND
 CAP AT THE MAIN
 -SHOW ALL DRY UTILITIES WITHIN PROJECT LIMITS
 -PROVIDE CCTV TO CONFIRM LATERAL LOCATIONS
 -DENOTE SAMPLE POINT LOCATIONS
 -PROVIDE ALL UTILITY CROSSINGS
 -PROVIDE DEMAND CALCULATIONS IN ORDER TO DETERMINE
 SUFFICIENT INCOMING FLOW FROM EXISTING MAIN
 -PROVIDE SOFT DIG INFORMATION AT POINTS OF CONNECTION