Plan Review Notes
Plan Review Notes For Project Z22070019
Project Number Z22070019
Review Stop STORM
Sequence Number 1
Notes
Date Text
2022-08-12 10:26:08THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO
 NGVD1929 ON THE SURVEY. LIST THE REFERENCED VERTICAL
 DATUM AND CONVERSION EQUATION TO NGVD1929 ON ALL SHEETS
 WITH ELEVATION INFORMATION.
  
 2. SHOW THE EXISTING CATCH BASINS AND STORM PIPE ON
 51ST ST ON ALL OF THE PLAN SHEETS.
  
 3. EXISTING DRIVEWAY AND DROP CURB ON 51ST ST APPEARS
 WIDER THAN WHAT IS NEEDED FOR THE DEVELOPMENT. REMOVE
 THE EXCESS DRIVEWAY APRON AND DROP CURB AND REPLACE
 WITH LANDSCAPING AND TYPE F CURB AND GUTTER (INCLUDING
 TRANSITIONS TO DROP CURB). SHOW CURB AND GUTTER ON 51ST
 ST AND ON BROADWAY AVE.
  
 4. BROADWAY AVE IS MAINTAINED BY FDOT. ANY IMPROVEMENTS
 WITH THE BROADWAY AVE ARE TO BE APPROVED BY FDOT.
 COORDINATE WITH FDOT THE EXISTING CURB CUTS ON BROADWAY
 AVE.
  
 5. DRAWING NO. S-100
 A. CAN YOU PROVIDE A COPY OF THE TOPOGRAPHIC SURVEY BY
 PREMIER DESIGN SOLUTIONS INC. REFERENCED IN THE FIFTH
 PARAGRAPH UNDER GENERAL NOTES?
 B. CAN YOU PROVIDE THE CTA SURVEY REFERENCED IN THE
 FIRST PARAGRAPH UNDER CITY OF WEST PALM BEACH WATER
 MAIN SYSTEM NOTES?
 C. MINIMUM DEPTH OF COVER FOR ALL WATER MAINS IS 36
 INCHES.
 D. "MAXIMUM DEFECTION (SIC) PER EACH JOINT SHALL BE 3'
 WHERE DEFLECTION IS REQUIRED." WHAT DOES THIS MEAN?
 E. TWO DIFFERENT PHONE NUMBERS LISTED FOR ONE CALL
 SUNSHINE.
 F. MINIMUM CLEARANCE BETWEEN STORM STRUCTURES AND WATER
 MAINS SHALL BE 3 FEET, NOT 2 FEET.
 G. MINIMUM VERTICAL CLEARANCE FOR WATER MAINS PASSING
 UNDER OTHER UTILITIES IS 12 INCHES (OUTSIDE WALL TO
 OUTSIDE WALL), NOT 18 INCHES.
  
 6. DRAWING NO. S-101
 A. UNDER "GENERAL CONDITIONS" 'REPLANTING' OR
 'REPLATTING'
 B. UNDER "CIVIL DESIGN CRITERIA" - WHAT AGENCY GOES BY
 THE LETTERS S.F.W.M.D.C.?
 C. UNDER "APPLICABLE CODES" - NAVD1988 IS THE
 ABBREVIATION FOR NORTH AMERICAN VERTICAL DATUM 1988.
 NGVD1929 IS NATIONAL GEODETIC VERTICAL DATUM 1929.
 D. UNDER "TEMPORARY FACILITIES" - REMOVE REFERENCE TO
 POMPANO BEACH.
 E. UNDER "STORM DRAINAGE INSTALLATIONS:", WHAT IS BCPS?
  
 7. DRAWING NO. S-200:
 A. LABEL THE PARALLEL LINES RUNNING EAST-WEST AND
 NORTH-SOUTH THROUGH THE SIDEWALK AND DRIVEWAY ALONG
 51ST STREET.
 B. SEVERAL PROPOSED SPOT GRADES ON THE SIDEWALKS ARE
 LISTED AS F.F.E.
 C. WHAT DOES THE 'X+' REPRESENT FOR THE EXISTING AND
 PROPOSED ELEVATIONS?
 D. PROVIDE EXISTING SPOT GRADES ALONG THE EDGE OF
 PAVEMENT OF BROADWAY AVE AND 51ST ST
 E. PROVIDE EXISTING SPOT GRADES ALONG THE SOUTH AND
 WEST PROPERTY LINES.
 F. PROVIDE CROSS SECTIONS FOR ALL FOUR PROPERTY LINES.
 EXTEND FROM FACE OF THE BUILDING TO 5 FEET BEYOND THE
 SOUTH AND WEST PROPERTY LINES AND TO THE CENTERLINES OF
 BROADWAY AVE AND 51ST ST. SHOW AND LABEL PROPERTY
 LINES, STREET R/W NAME, ALL GRADE BREAKS AND SURFACE
 FEATURES (FENCE, SIDEWALK, CURB AND GUTTER,
 LANDSCAPING, SIDEWALK, BUILDING WALL AND F.F.E.).
 PROVIDE DIMENSIONS FROM PROPERTY LINE TO THE SURFACE
 FEATURES.
  
 8. DRAWING NO. S-202
 A. PARKING STRIPE DETAIL - CITY STANDARD IS PARALLEL 4
 INCH STRIPES SEPARATED BY 12 INCHES CLEAR AND JOINED AT
 ONE END WITH A 4 INCH STRIPE. DETAIL ON THE PLANS SHOWS
 16 INCH CLEAR SPACE WITH NO CONNECTING STRIPE.
 B. NORTH EDGE OF STOP BAR STRIPE SHOULD BE 4 FEET FROM
 THE BACK OF SIDEWALK. PLAN SHOWS THE SOUTH EDGE AT 4
 FEET FROM THE BACK OF SIDEWALK.
 C. HANDICAP SIGN MISSPELLED (SING).
 D. WHAT ARE THE PROPOSED 24 INCH WHITE STRIPES CALLED
 OUT ON THE RIGHT SIDE OF THE PLAN VIEW?
  
 9. DRAWING NO. S-204:
 A. SHOW LIMITS OF MILLING AND RESURFACING
 B. CALL OUT AN EASEMENT FOR THE WATER METER AND SEWER
 CLEANOUT.
 C. PVC MISSPELLED (PCV) FOR 6 INCH LATERAL.
  
 10. DRAWING NO. C-500, STANDARD DETAIL ST-8 - CONFIRM
 THE 20 FEET DEPTH IN THE TRENCH SCHEDULE.
  
 11. DRAWING NO. C-501: DRAINAGE TABLE -
 A. SWITCH COLUMN HEADINGS FOR NORTH AND SOUTH.
 B. SWITCH COLUMN HEADINGS FOR EAST AND WEST.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  