| 2022-08-05 17:58:43 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -THE FIRST SURVEY GENERAL NOTE SAYS NO SEARCH OF PUBLIC |
| | RECORD HAS BEEN MADE. WHEN WILL SEARCH BE CONDUCTED? |
| | -FOR ENGINEERING DEVELOPMENT SUBMITTAL: VERIFY WATER |
| | MAIN PIPE SIZE AND MATERIAL TYPE ? WPB GIS SAYS 6 INCH |
| | CAST IRON FROM 1926; VERIFY SANITARY SEWER MAIN PIPE |
| | SIZE AND MATERIAL TYPE ? WPB GIS SAYS 12 INCH VCP FROM |
| | 1925; VERIFY LOCATION OF WATER AND SEWER MAINS. |
| | -ADD VISUAL MEASUREMENT SCALE ICONS TO CIVIL PLAN |
| | SHEETS. |
| | -ADD GATE VALVE ON PROPOSED FIRELINE JUST INSIDE |
| | PROPERTY LINE. LABEL IT FIRELINE POINT OF SERVICE GATE |
| | VALVE. |
| | -CITY DOES NOT OFFER 1.25 INCH WATER METERS. COULD DO |
| | EITHER 1 INCH METER WITH 1 INCH SERVICE LINE OR 1.5 |
| | INCH METER WITH 2 INCH SERVICE LINE. |
| | -CALLOUT FIRELINE PIPE BETWEEN TAP AND PROPERTY LINE AS |
| | DIP. ALSO ADD SIZE TO THAT LABEL. |
| | -ENLARGED WATER SEWER PLAN SHOWS BUSH AND WATER METER |
| | BOX OVERLAPPING. PLEASE PROVIDE CLEARANCE DISTANCE. |
| | -ON WATER SEWER PLAN, CALLOUT THE MINIMUM HORIZONTAL |
| | CLEARANCE DISTANCE BETWEEN THE TWO WATER TAPS. ALSO |
| | CALLOUT THE MINIMUM HORIZONTAL CLEARANCE DISTANCE |
| | BETWEEN THE SANITARY SEWER SERVICE AND FIRELINE WATER |
| | SERVICE. |
| | -ON CIVIL PLANS, CLEARLY SHOW THE TERMINAL ENDS OF THE |
| | 6 FOOT WOODEN FENCE NEAR THE SOUTHEAST AND NORTHWEST |
| | AREAS OF PROPERTY. ENSURE FENCE DOES NOT CONFLICT WITH |
| | BACKFLOW ASSEMBLIES. |
| | -SHOW BOUNDARIES OF PAVEMENT RESTORATION ON 51ST ST |
| | RELATED TO THE PROPOSED UTILITY WORK. BOUNDARIES SHOULD |
| | COMPLY WITH STANDARD DETAIL P-4. |
| | -ON WATER PLAN, SHOW AND LABEL THE NEAREST FIRE |
| | HYDRANT. |
| | -SHOW FULL WIDTH OF 51ST ST INCLUDING OPPOSITE CURB |
| | AREA. |
| | -APPLICANT MAY BE REQUIRED TO UPGRADE EXISTING WATER OR |
| | SEWER MAINS UPON REVIEW OF CITY OR EOR AT ENGINEERING |
| | DEVELOPMENT SUBMITTAL. |
| | -DID NOT SEE FDC ON CIVIL PLANS. IF IT IS NEEDED OR |
| | REQUIRED, SHOW AND LABEL IT. VERIFY IT IS AN ACCEPTABLE |
| | DISTANCE FROM NEAREST FIRE HYDRANT. |
| | -SHOW AND LABEL PROPOSED UTILITY EASEMENT. BACKFLOW |
| | ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENT. |
| | -VERIFY NO AUXILIARY WATER SUPPLIES SUCH AS WELLS WILL |
| | BE CONNECTED TO FIRE SYSTEM. |
| | -SITE PLAN SHOWS AN EASEMENT NEAR EAST PROPERTY LINE. |
| | WHAT TYPE OF EASEMENT IS IT? ALSO SHOW THE BOUNDARIES |
| | MORE CLEARLY. |
| | -HISTORIC PICTURES SHOW OVERHEAD UTILITIES NEAR SOUTH |
| | PROPERTY LINE EXTENDING OUT NORTH FROM POLES. WILL |
| | PROPOSED BUILDING ENCROACH ON THEM? |
| | -PROPERTY APPRAISER SHOWS ADDRESS AS 5111 BROADWAY. IS |
| | THE ADDRESS CHANGING? |
| | -SHOW AND LABEL ALL EXISTING UTILITIES SUCH AS EXISTING |
| | METER BOX NEAR NORTHWEST AREA OF PROPERTY AND CLEANOUTS |
| | LABELED ON SURVEY. ADD WHAT IS HAPPENING TO THEM ON |
| | LABELS. |
| | -SHOW AND LABEL ANY PROPOSED GREASE TRAPS IF THEY ARE |
| | OUTSIDE BUILDING. |
| | -VERIFY IF THERE IS AN EXISTING UTILITY EASEMENT ALONG |
| | SOUTH SIDE OF PROPERTY. |
| | -VERIFY DIRECTION FACING ON A2-1.02, A2 1.03, A2 1.04 |
| | -POSITION OF TREES BETWEEN DIFFERENT PLAN SETS DOES NOT |
| | LOOK SIMILAR. PLEASE MAKE SURE ALL PLANS SETS SHOW |
| | UTILITIES AND TREES IN THE SAME POSITIONS. ENSURE THERE |
| | IS ADEQUATE SPACING BETWEEN THEM. |
| | -WILL IRRIGATION ALSO RUN OFF THE DOMESTIC WATER |
| | SERVICE? |
| | -SHOW AND LABEL EXISTING STORMWATER UTILITIES INCLUDING |
| | THE STRUCTURES AND PIPE ON 51ST ST. |
| | -AT THE DATUM STATEMENTS ON EACH SHEET ALSO ADD |
| | CONVERSION EQUATION. |
| | -HISTORIC PICTURES SHOW COUPLE OF DRIVEWAY APPROACHES |
| | AT EAST SIDE OF PROPERTY. VERIFY THE INTENTION IS TO |
| | ADD CURBING AND SHOW THAT BETTER ON PLANS. |