2022-08-05 17:58:43PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -THE FIRST SURVEY GENERAL NOTE SAYS NO SEARCH OF PUBLIC
 RECORD HAS BEEN MADE. WHEN WILL SEARCH BE CONDUCTED?
 -FOR ENGINEERING DEVELOPMENT SUBMITTAL: VERIFY WATER
 MAIN PIPE SIZE AND MATERIAL TYPE ? WPB GIS SAYS 6 INCH
 CAST IRON FROM 1926; VERIFY SANITARY SEWER MAIN PIPE
 SIZE AND MATERIAL TYPE ? WPB GIS SAYS 12 INCH VCP FROM
 1925; VERIFY LOCATION OF WATER AND SEWER MAINS.
 -ADD VISUAL MEASUREMENT SCALE ICONS TO CIVIL PLAN
 SHEETS.
 -ADD GATE VALVE ON PROPOSED FIRELINE JUST INSIDE
 PROPERTY LINE. LABEL IT FIRELINE POINT OF SERVICE GATE
 VALVE.
 -CITY DOES NOT OFFER 1.25 INCH WATER METERS. COULD DO
 EITHER 1 INCH METER WITH 1 INCH SERVICE LINE OR 1.5
 INCH METER WITH 2 INCH SERVICE LINE.
 -CALLOUT FIRELINE PIPE BETWEEN TAP AND PROPERTY LINE AS
 DIP. ALSO ADD SIZE TO THAT LABEL.
 -ENLARGED WATER SEWER PLAN SHOWS BUSH AND WATER METER
 BOX OVERLAPPING. PLEASE PROVIDE CLEARANCE DISTANCE.
 -ON WATER SEWER PLAN, CALLOUT THE MINIMUM HORIZONTAL
 CLEARANCE DISTANCE BETWEEN THE TWO WATER TAPS. ALSO
 CALLOUT THE MINIMUM HORIZONTAL CLEARANCE DISTANCE
 BETWEEN THE SANITARY SEWER SERVICE AND FIRELINE WATER
 SERVICE.
 -ON CIVIL PLANS, CLEARLY SHOW THE TERMINAL ENDS OF THE
 6 FOOT WOODEN FENCE NEAR THE SOUTHEAST AND NORTHWEST
 AREAS OF PROPERTY. ENSURE FENCE DOES NOT CONFLICT WITH
 BACKFLOW ASSEMBLIES.
 -SHOW BOUNDARIES OF PAVEMENT RESTORATION ON 51ST ST
 RELATED TO THE PROPOSED UTILITY WORK. BOUNDARIES SHOULD
 COMPLY WITH STANDARD DETAIL P-4.
 -ON WATER PLAN, SHOW AND LABEL THE NEAREST FIRE
 HYDRANT.
 -SHOW FULL WIDTH OF 51ST ST INCLUDING OPPOSITE CURB
 AREA.
 -APPLICANT MAY BE REQUIRED TO UPGRADE EXISTING WATER OR
 SEWER MAINS UPON REVIEW OF CITY OR EOR AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
 -DID NOT SEE FDC ON CIVIL PLANS. IF IT IS NEEDED OR
 REQUIRED, SHOW AND LABEL IT. VERIFY IT IS AN ACCEPTABLE
 DISTANCE FROM NEAREST FIRE HYDRANT.
 -SHOW AND LABEL PROPOSED UTILITY EASEMENT. BACKFLOW
 ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENT.
 -VERIFY NO AUXILIARY WATER SUPPLIES SUCH AS WELLS WILL
 BE CONNECTED TO FIRE SYSTEM.
 -SITE PLAN SHOWS AN EASEMENT NEAR EAST PROPERTY LINE.
 WHAT TYPE OF EASEMENT IS IT? ALSO SHOW THE BOUNDARIES
 MORE CLEARLY.
 -HISTORIC PICTURES SHOW OVERHEAD UTILITIES NEAR SOUTH
 PROPERTY LINE EXTENDING OUT NORTH FROM POLES. WILL
 PROPOSED BUILDING ENCROACH ON THEM?
 -PROPERTY APPRAISER SHOWS ADDRESS AS 5111 BROADWAY. IS
 THE ADDRESS CHANGING?
 -SHOW AND LABEL ALL EXISTING UTILITIES SUCH AS EXISTING
 METER BOX NEAR NORTHWEST AREA OF PROPERTY AND CLEANOUTS
 LABELED ON SURVEY. ADD WHAT IS HAPPENING TO THEM ON
 LABELS.
 -SHOW AND LABEL ANY PROPOSED GREASE TRAPS IF THEY ARE
 OUTSIDE BUILDING.
 -VERIFY IF THERE IS AN EXISTING UTILITY EASEMENT ALONG
 SOUTH SIDE OF PROPERTY.
 -VERIFY DIRECTION FACING ON A2-1.02, A2 1.03, A2 1.04
 -POSITION OF TREES BETWEEN DIFFERENT PLAN SETS DOES NOT
 LOOK SIMILAR. PLEASE MAKE SURE ALL PLANS SETS SHOW
 UTILITIES AND TREES IN THE SAME POSITIONS. ENSURE THERE
 IS ADEQUATE SPACING BETWEEN THEM.
 -WILL IRRIGATION ALSO RUN OFF THE DOMESTIC WATER
 SERVICE?
 -SHOW AND LABEL EXISTING STORMWATER UTILITIES INCLUDING
 THE STRUCTURES AND PIPE ON 51ST ST.
 -AT THE DATUM STATEMENTS ON EACH SHEET ALSO ADD
 CONVERSION EQUATION.
 -HISTORIC PICTURES SHOW COUPLE OF DRIVEWAY APPROACHES
 AT EAST SIDE OF PROPERTY. VERIFY THE INTENTION IS TO
 ADD CURBING AND SHOW THAT BETTER ON PLANS.