2022-08-05 19:11:13PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -VERIFY THAT THE PROPOSED BUILDING WILL NOT HAVE FIRE
 SPRINKLERS.
 -VERIFY THAT EXISTING WATER SERVICE IS SUFFICIENT FOR
 PROPOSED BUILDING.
 -VERIFY THAT WASTEWATER USED BY PROPERTY WILL FLOW TO
 SEWER MANHOLE ON UP THE GROVE.
 -IS EXISTING LIFT STATION CURRENTLY FUNCTIONAL AND IN
 USE DAY TO DAY?
 -WILL THERE BE AN IRRIGATION SYSTEM AND WILL IT RUN OFF
 THE EXISTING METERED WATER SERVICE?
 -PROVIDE PLANS FOR THE PROPOSED LIFT STATION.
 -HAS FENCE BEEN REROUTED AROUND WATER METER BOX YET?
 -HISTORIC PICTURES SHOW GUY WIRES COMING OFF ONE OF THE
 LARGE UTILITY POLES NEAR NORTHWEST AREA OF PROPERTY. IF
 THEY ARE STILL THERE SHOW ON PLANS AND ENSURE NO
 LANDSCAPING CONFLICTS.
 -LANDSCAPING PLANS SHOW MORE ENCROACHMENTS INTO
 MAINTENANCE AND ACCESS EASEMENT. VERIFY THAT NORTHERN
 PBC IMPROVEMENT DISTRICT IS ALRIGHT WITH THE PROPOSED
 PLANS. ALSO VERIFY IF THEY CURRENTLY ACCESS THE AREA
 WITH VEHICLES OR MACHINERY. IF SO, ENSURE THAT THEY
 WILL CONTINUE TO BE ABLE TO AFTER PROJECT IS COMPLETE.
 -LANDSCAPING PLANS SHOW 30 FOOT SUBSTATION CLEAR ZONE.
 PLEASE DESCRIBE WHAT THAT IS AND VERIFY THAT THE CLEAR
 ZONE REQUIREMENTS WILL BE MET.