| Notes |
| Date |
Text |
| 2022-08-05 19:11:13 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -VERIFY THAT THE PROPOSED BUILDING WILL NOT HAVE FIRE | | | SPRINKLERS. | | | -VERIFY THAT EXISTING WATER SERVICE IS SUFFICIENT FOR | | | PROPOSED BUILDING. | | | -VERIFY THAT WASTEWATER USED BY PROPERTY WILL FLOW TO | | | SEWER MANHOLE ON UP THE GROVE. | | | -IS EXISTING LIFT STATION CURRENTLY FUNCTIONAL AND IN | | | USE DAY TO DAY? | | | -WILL THERE BE AN IRRIGATION SYSTEM AND WILL IT RUN OFF | | | THE EXISTING METERED WATER SERVICE? | | | -PROVIDE PLANS FOR THE PROPOSED LIFT STATION. | | | -HAS FENCE BEEN REROUTED AROUND WATER METER BOX YET? | | | -HISTORIC PICTURES SHOW GUY WIRES COMING OFF ONE OF THE | | | LARGE UTILITY POLES NEAR NORTHWEST AREA OF PROPERTY. IF | | | THEY ARE STILL THERE SHOW ON PLANS AND ENSURE NO | | | LANDSCAPING CONFLICTS. | | | -LANDSCAPING PLANS SHOW MORE ENCROACHMENTS INTO | | | MAINTENANCE AND ACCESS EASEMENT. VERIFY THAT NORTHERN | | | PBC IMPROVEMENT DISTRICT IS ALRIGHT WITH THE PROPOSED | | | PLANS. ALSO VERIFY IF THEY CURRENTLY ACCESS THE AREA | | | WITH VEHICLES OR MACHINERY. IF SO, ENSURE THAT THEY | | | WILL CONTINUE TO BE ABLE TO AFTER PROJECT IS COMPLETE. | | | -LANDSCAPING PLANS SHOW 30 FOOT SUBSTATION CLEAR ZONE. | | | PLEASE DESCRIBE WHAT THAT IS AND VERIFY THAT THE CLEAR | | | ZONE REQUIREMENTS WILL BE MET. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] | | | |
| |