2022-10-31 12:52:33PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -L0.1.01 AND A0.00 SHOW TREE OVER LARGE WATER SERVICE.
 TREE TRUNKS CANNOT BE LOCATED OVER WATER SERVICES AND
 MUST HAVE SUFFICIENT HORIZONTAL DISTANCE AWAY FROM
 THEM.
 -L0.1.01 AND A0.00 SHOW SQUARE OBJECT APPROX 22 FEET
 EAST OF THE NORTHEAST FIRELINE BACKFLOW ASSEMBLY.
 PLEASE LABEL WHAT IT IS ON THOSE PLANS AND ALSO SHOW
 AND LABEL IT ON THE CIVIL PLANS.
 -A0.00 SHOWS TREE EAST OF NORTHEAST FIRELINE BACKFLOW
 ASSEMBLY THAT MAY BE TOO CLOSE TO THE SERVICE LINE.
 PLEASE ENSURE THERE IS SUFFICIENT CLEARANCE DISTANCE.
 -SOME OF THE CALLOUTS AND LABELING ON THE UTILITY PLANS
 NEED TO BE REVISED, SUCH AS THOSE FOR THE BACKFLOW
 ASSEMBLY TYPES, WATER METERS, AND THE WATER SERVICE
 PIPE SIZES. CAN UPDATE NOW OR AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
 -WILL THE CONNECTION ROAD RUNNING FROM ALLEY TO BUTLER
 UNDERNEATH THE BUILDING HAVE SOME KIND OF ACCESS
 EASEMENT? DID NOT SEE ANY SHOWN OR LABELED ON PLANS.