Plan Review Notes For Project Z22070008
Project Number Z22070008
Review Stop STORM
Sequence Number 3
Notes
Date Text
2022-10-20 16:25:15OLARA (Z22070008) STORM #3
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 9/30/2022.. PREVIOUSLY SATISFIED COMMENTS ARE NOT
 INCLUDED.
  
  
 1. [SATISFIEDL] THE CITY???S OFFICIAL VERTICAL DATUM IS
 NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 AS
 LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE VERTICAL
 DATUM CONVERSION TO NGVD1929 ON THE SURVEY.
  
 3. [PARTIALLY SATISFIED] DRAINAGE CALCULATIONS TO
 CONSIDER SEA LEVEL RISE ON THE GROUNDWATER TABLE AND
 TAILWATER CONDITIONS. ADDITIONAL COMMENTS: ??? EXPLAIN
 HOW SEA LEVEL RISE WAS CONSIDERED IN THE DESIGN AND
 DRAINAGE CALCULATIONS. GROUNDWATER WILL INCREASE WITH
 SEA LEVEL RISE. THE FLAP GATE WILL NOT BE NEEDED ???
 THE WEIR SHOULD PREVENT BACKFLOW INTO THE ONSITE
 DRAINAGE SYSTEM.
  
 4. [PARTIALLY SATISFIED] JUSTIFY THE DIAMETER OF THE
 OUTFALL PIPE. ADDITIONAL COMMENTS: WHAT WAS ASSUMED AS
 THE DOWNSTREAM HGL ELEVATION (AT STRUCTURE ST-31)? IF
 THE OUTFALL PIPE NEEDS TO BE 18??? DIAMETER, THEN THE
 EXISTING 15??? RCP BETWEEN ST-31 AND THE EXISTING
 MANHOLE WILL NEED TO BE UPSIZED. THE HORIZONTAL
 CLEARANCE BETWEEN THIS PROPOSED REPLACEMENT PIPE AND
 THE EXISTING SANITARY SEWER MANHOLE WILL NEED TO BE
 VERIFIED AS WELL AS THE EXISTING STORM MANHOLE IS LARGE
 ENOUGH TO BE MODIFIED TO CONNECT THE PROPOSED
 REPLACEMENT PIPE. NOTE THE CONTROL STRUCTURE TOP SLAB
 MAY CONSTRICT THE 25-YEAR 3-DAY FLOW OVER THE WEIR.
  
  
 11. [PARTIALLY SATISFIED] SHOW HOW ALLEY GRADING WILL
 TRANSITION TO EXISTING GRADE. ADDITIONAL COMMENTS: THE
 ALLEY APPEARS TO SLOPE FROM WEST TO EAST AND AT THE
 EAST END THE PROPOSED GRADES DIRECT THE WATER TO THE
 SOUTHEAST CORNER OF THE NEW END OF THE ALLEY. HOW WILL
 THE STORMWATER RUNOFF BE PREVENTED FROM FLOWING ONTO
 THE ADJACENT PROPERTY?
  
 15. [PARTIALLY SATISFIED] LABEL EXISTING UTILITIES IN
 THE RIGHT OF WAY (PIPE SIZE, MATERIAL, ETC.) ADDITIONAL
 COMMENT: STORM PIPE ON PINE STREET IS LABELED AS 48???
 AND 54??? RCP. LABEL THE PINE STREET SEWER MAINS ON
 SHEET C-500.
  
 17. [NOT SATISFIED] PROVIDE PROPOSED FINISHED FLOOR
 ELEVATIONS ON THE PGD PLANS. ADDITIONAL COMMENT:
 FFE???S WERE REMOVED ON SHEET C-500 IN THE 9/30/22
 SUBMITTAL.
  
 18. [PARTIALLY SATISFIED ??? INCLUDE MILL AND RESURFACE
 HATCHING IN THE SHEET LEGENDS.] SHOW MILL AND
 RESURFACING LIMITS AND PAVEMENT MARKINGS WITHIN THESE
 LIMITS. ADDITIONAL COMMENT: SHEET C-600 SHOWS PROPOSED
 UTILITIES CROSSING N. FLAGLER DRIVE BUT THERE IS NO
 INDICATION OF MILL AND RESURFACING ON SHEET C-500.
  
 21. [PARTIALLY SATISFIED] PROVIDE ADDITIONAL EXISTING
 GRADES ALONG THE EP OF N. FLAGLER DRIVE, NORTH OF THE
 PROPOSED DRIVEWAY. ADDITIONAL COMMENT: REVIEW THE
 PROPOSED GRADING FOR THE DRIVEWAY TO N. FLAGLER DRIVE.
 THERE WILL BE A LOW POINT BETWEEN TWO HIGH POINTS ALONG
 THE EP AT THE NORTH SIDE OF THE DRIVEWAY.
  
 NEW COMMENTS (8/26/2022 SUBMITTAL)
  
 22. [SATISFIED] SECTION A-A
  A. BEGINNING OF DRIVEWAY SHOULD MEET EXISTING GRADE.
  B. VALLEY GUTTER MAY NOT BE NEEDED.
  C. CREATE A HIGH POINT IN THE DRIVEWAY AT THE BACK OF
 SIDEWALK AND ELIMINATE THE TRENCH DRAIN. ADD A CATCH
 BASIN ONTO THE 18 INCH STORM PIPE TO COLLECT RUNOFF
 WITHIN THE BUILDING.
  
 23. [PARTIALLY SATISFIED] SECTION C-C
  A. MOVE SECTION ABOUT 20 FEET TO THE WEST TO FALL
 WITHIN THE LANDSCAPE AREA BETWEEN THE SIDEWALKS AND
 THROUGH THE SEATWALLS.
  B. FG LINE APPEARS TO BE SHIFTED TO THE RIGHT. IF NOT
 THEN ABOUT 5 FEET OF SIDEWALK CROSS SLOPE IS TOO STEEP.
  C. CONFIRM PROPOSED GRADE OF 6.01 (VS. 6.10 ON PGD
 PLAN).
  D. R/W DIMENSIONS ADD UP TO LESS THAN 37.5 FEET.
  E. THE FLOOR OF THE BUILDING INTERIOR APPEARS TO HAVE
 10% SLOPE.
  F. SHEET A0.08 SHOWS A DOOR OPENING TO THE CAF?? SPACE
 WHERE THE PGD PLAN SHOWS SPOT GRADES BETWEEN 8.03 FEET
 AND 6.34 FEET NAVD ADJACENT TO THE BUILDING. CAF?? FFE
 IS 9.00 FEET NAVD.
 ADDITIONAL COMMENTS:
  G. GRADES SHOWN FOR 9.4??? SIDEWALK RESULT IN CROSS
 SLOPE STEEPER THAN 2%.
  H. LIMIT SLOPE OF LANDSCAPE AREA TO 4:1 OR FLATTER.
 INDICATED SLOPE OF 17% IS OK.
  
 24. [PARTIALLY SATISFIED] SECTION D-D
  A. NOT SHOWN ON KEY MAP.
  B. BEGINNING OF DRIVEWAY SHOULD MEET EXISTING GRADE.
 ADDITIONAL COMMENTS:
  C. SHOW DROP CURB AT BEGINNING OF THE 14.8 FT DRIVEWAY
 APRON.
  
 25. [PARTIALLY SATISFIED] SECTION F-F
  A. CREATE A HIGH POINT IN THE DRIVEWAY AT THE
 PROPERTY/RIGHT OF WAY LINE, CONVERT ST-29 TO A CATCH
 BASIN AND ELIMINATE THE TRENCH DRAIN. THIS WILL ALLOW
 ST-29 TO BE SMALLER THAN 7 FEET IN DIAMETER BY
 ELIMINATING THE SOUTH PIPE CONNECTION.
  B. R/W DIMENSIONS ADD UP TO LESS THAN 25 FEET.
 ADDITIONAL COMMENTS:
  C. CONFIRM THE 8.63 FT NAVD SPOT GRADE. PGD PLAN SHOWS
 DRIVEWAY EP BETWEEN 8.62 FT AND 8.28 FT NAVD. TRIM
 BLACK LINE TO BACK OF VALLEY GUTTER.
  D. SHOW/DIMENSION THE LOCATION OF THE
 SIDEWALK/CROSSWALK THROUGH THE DRIVEWAY.
  
 26. [SATISFIED] SECTION G-G
  A. DIMENSIONS DO NOT MATCH WHAT IS SHOWN ON SHEET
 C-400.
  B. SECTION SYMBOL ON KEY MAP SHOULD POINT TO THE WEST.
  C. WILL SIDEWALK HAVE A THICKENED EDGE? PROVIDE A
 DETAIL OF THE SIDEWALK IF SO.
  D. SHOW HEIGHT OF SITE WALL.
  E. CREATE A SWALE OR BERM ALONG THE PROPERTY LINE TO
 PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY.
  F. SHOW CURBING ADJACENT TO THE ISLAND AND IN-BOUND
 DRIVEWAY.
  
 27. [PARTIALLY SATISFIED] SECTION H-H
  A. SHOW HEIGHT OF SITE WALLS.
  B. WHY CAN???T THE FRONT OF SIDEWALK NEAREST THE R/W
 MATCH EXISTING GRADE?
  C. CREATE SWALE BEHIND EAST SITE WALL TO PREVENT
 RUNOFF FROM FLOWING ONTO SIDEWALK.
 ADDITIONAL COMMENT:
  D. CREATE SWALES/DEPRESSIONS IN EACH OF THE LANDSCAPE
 AREAS.
  
 28. [SATISFIED] PROVIDE DETAIL SHOWING 18-INCH PIPE
 CONNECTION TO TRENCH DRAIN.
  
 29. [SATISFIED] SECTION G-G SHOWS THE DRIVEWAY SLOPING
 TO THE NORTH. THE TRENCH DRAIN ACROSS N. FLAGLER
 DRIVEWAY NEEDS TO EXTEND TO NORTH CURB LINE.
  
 30. [PARTIALLY SATISFIED] CONSIDER ADDING TRENCH DRAIN
 ALONG NORTH CURB LINE WEST OF THE SIDEWALK CROSSING OF
 THE N. FLAGLER DRIVEWAY TO REDUCE THE AMOUNT OF RUNOFF
 FLOWING ACROSS THE SIDEWALK CROSSING. ADDITIONAL
 COMMENT: DUE TO THE CROSS SLOPE OF THE DRIVEWAY, ALL OF
 THE RUNOFF WILL FLOW ALONG THE NORTH CURB LINE OF THE
 DRIVEWAY. THE SUGGESTION IS THE ADD TRENCH DRAIN ALONG
 THE NORTH CURB LINE, WEST OF THE CROSSWALK ACROSS THE
 DRIVEWAY, TO COLLECT THE RUNOFF BEFORE IT FLOWS ACROSS
 THE CROSSWALK. A SECOND SUGGESTION IS TO HAVE A CURB
 CUT AND FLUME TO THE YARD DRAIN IN THE 17 FT WIDE
 LANDSCAPE AREA/SWALE.
  
 31. [PARTIALLY SATISFIED ??? SHOW THE CONCRETE APRONS
 ON THE CROSS SECTIONS] DRIVEWAY APRONS WITHIN THE RIGHT
 OF WAY SHOULD BE CONCRETE.
  
 32. [SATISFIED ??? CAN MH (RENUMBERED AS SS-01) GO IN
 THE SIDEWALK INSTEAD OF DRIVEWAY? DRIVEWAY EXIT WILL BE
 BLOCKED WHEN THE MH IS OPENED.] CONSIDER MOVING
 SANITARY MANHOLE SS-05 OUT OF THE DRIVEWAY AND OUT OF
 THE SIDEWALK. COORDINATE WITH THE PUBLIC UTILITIES
 DEPARTMENT.
  
 33. [SATISFIED] REMOVE STRUCTURES ST-28 AND ST-34 OUT
 OF THE ALLEY R/W.
  
 34. [SATISFIED] SOUTH EDGE OF ALLEY NEEDS TO MEET
 EXISTING GRADE AT RIGHT OF WAY.
  
 35. [SATISFIED] WILL SIDEWALK AT DROPOFF AREA BE FLUSH
 WITH PAVEMENT AND/OR HAVE THICKENED EDGE?
  
 NEW COMMENTS (9/30/22 SUBMITTAL):
  
 36. THE EXISTING 15-INCH CAST IRON (CAS) SANITARY SEWER
 MAIN IS NOT SHOWN GOING THROUGH STRUCTURE SS-EX-01. ARE
 PIPE INVERTS FOR SS-EX-01 AVAILABLE?
  
 37. CHECK GRADING OF THE EAST END OF THE PROPOSED
 SIDEWALK ON BUTLER ST. CROSS SLOPE SHOULD NOT EXCEED
 2%. LONGITUDINAL SLOPE SHOULD NOT EXCEED 5%.
  
 38. ON THE DEMOLITION PLANS, INDICATE WHAT WILL HAPPEN
 TO THE STREET LIGHT POLES. THERE IS A LIGHT POLE
 OPPOSITE BROWARD AVE.
  
 39. EXISTING FIRE HYDRANT ON NE CORNER OF BROWARD AVE
 AND BUTLER ST IS SHOWN IN THE SIDEWALK.
  
 40. INCLUDE IN THE LEGEND THE SYMBOL SOUTH OF THE
 PROPOSED FIRE HYDRANT ASSEMBLY #1. THE SYMBOL CONSISTS
 OF A CIRCLE WITH A PLUS SIGN.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  