| 2022-10-05 07:48:50 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | -SHOW AND LABEL EXISTING SEWER LATERAL AT 1900 N DIXIE |
| | HWY TO ENSURE THEY WILL STILL HAVE FUNCTIONING |
| | WASTEWATER SERVICE. |
| | -SHEET C1.01 SAYS 300 BUTLER SEWER LATERAL TO REMAIN, |
| | BUT ALSO SAYS SANITARY SEWER MAIN IS BEING REMOVED. |
| | PLEASE ENSURE THAT PROPERTY WILL STILL HAVE FUNCTIONING |
| | WASTEWATER SERVICE. |
| | -REMINDER: SHEET C602 AND C600: LABEL SANITARY SEWER |
| | MAIN RUNNING NORTH AT BUTLER AND BROWARD INTERSECTION |
| | WITH PIPE SIZE AND MATERIAL TYPE. |
| | -RESPONSE LETTER SAID THIS WAS CORRECTED, BUT DESIGN |
| | STILL LOOKS DIFFERENT: SHEET C500 DOES NOT MATCH |
| | HARDSCAPE PLAN L3-1-01 WITH RESPECT TO THE SIDEWALK |
| | DESIGN AT WEST SIDE OF FLAGLER ADJACENT TO SOUTHEAST |
| | CORNER OF 1923 N FLAGLER DR. |
| | -3 INCH AND 4 INCH WATER METERS REQUIRE DIP. ALSO 3 |
| | INCH METER HAS 4 INCH WATER SERVICE PIPE AND TAP PER |
| | STANDARD DETAILS. PLEASE UPDATE C602. |
| | -COVER SHEET SAYS THERE IS A SHEET C630, BUT THAT SHEET |
| | IS MISSING FROM PLAN SET. |
| | -SCREENING BUSHES AROUND 3 AND 4 INCH METERS CANNOT BE |
| | ON TOP OF GATE VALVES BOXES OR TOO CLOSE TO THEM. MUST |
| | BE ABLE TO OPERATE WITH VALVE KEY. HANDLES EXTEND |
| | APPROX 1.5 FEET HORIZONTAL FROM VALVE BOX. |
| | -A000 SHOWS TREE IN SIDEWALK EAST OF N. FLAGLER DR. |
| | TRIED TO VERIFY ON L5101, BUT SIDEWALK IS NOT SHOWING. |
| | WILL THERE BE TREE IN SIDEWALK? |
| | -NOTE WAS ADDED ON ENGINEERING PLANS SAYING CONTRACTOR |
| | SHALL PLACE ALL PROPOSED UTILITIES UNDERGROUND. UPDATE |
| | WORDING ON THAT NOTE TO CONTRACTOR SHALL PLACE ALL |
| | PROPOSED DRY UTILITIES UNDERGROUND. |
| | -AT SOUTHWEST AREA OF BUILDING ON A101 THERE IS A ROOM |
| | LABELED DIESEL 230SF. PLEASE DESCRIBE WHAT IT IS AND |
| | PROVIDE SHEET REFERENCE NUMBER THAT HAS MORE |
| | INFORMATION ON IT. |