Plan Review Notes
Plan Review Notes For Project Z22070008
Project Number Z22070008
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-10-18 16:47:31THE FOLLOWING NOTES WERE NOT ABLE TO BE INPUT INTO
 COMMUNITY PLUS AT THE TIME OF REVIEW DUE TO THE IT
 ISSUES WITH COMMUNITY PLUS. THE COMMENTS WERE EMAILED
 TO THE CONSULTANT AND ARE BEING ADDED TO COMMUNITY PLUS
 ON 10/18/2022 AS STORM #2. STORM #3 COMMENTS WILL
 ADDRESS THE 9/30/2022 RE-SUBMITTAL.
  
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 8/26/2022 SUBMITTAL.
  
  
 1. [NOT SATISFIED ??? REVISED SURVEY NOT INCLUDED IN
 THE SUBMITTAL] THE CITY???S OFFICIAL VERTICAL DATUM IS
 NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 AS
 LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE VERTICAL
 DATUM CONVERSION TO NGVD1929 ON THE SURVEY.
  
 2. [SATISFIED] MOVE THE TRENCH DRAIN OUTSIDE THE RIGHT
 OF WAY OF PINE STREET.
  
 3. [PARTIALLY SATISFIED ??? EXPLAIN HOW SEA LEVEL RISE
 WAS CONSIDERED] DRAINAGE CALCULATIONS TO CONSIDER SEA
 LEVEL RISE ON THE GROUNDWATER TABLE AND TAILWATER
 CONDITIONS.
  
 4. [NOT SATISFIED] JUSTIFY THE DIAMETER OF THE OUTFALL
 PIPE.
  
 5. [SATISFIED] WHAT WILL BE THE CONTRIBUTING AREA TO
 THE EXFILTRATION TRENCH UNDER THE DRIVEWAY TO N.
 FLAGLER DRIVE. THE HEAD ON THE TRENCH WILL BE LIMITED
 TO THE TRENCH DRAIN RIM ELEVATION.
  
 6. [SATISFIED] DESIGN ACCESS (HEIGHT CLEARANCE) TO
 EXFILTRATION TRENCH SYSTEMS FOR MAINTENANCE AND FUTURE
 REPLACEMENT WHEN THE EXFILTRATION TRENCHES ARE NO
 LONGER FUNCTIONING AS DESIGNED.
  
 7. [SATISFIED] SIDEWALK AND PARKING EASEMENTS WILL BE
 NEEDED FOR SIDEWALKS AND ON-STREET PARKING SPACES
 OUTSIDE THE RIGHT OF WAY.
  
 8. [SATISFIED ??? NOTE PIPE INVERTS DO NOT MATCH PLAN
 VIEW] PROVIDE DETAIL OF CONTROL STRUCTURE AND SHOW THE
 WEIR ELEVATION ON THE PGD PLANS.
  
 9. [SATISFIED] BLEEDERS ARE NOT PERMITTED WITH
 EXFILTRATION TRENCH SYSTEMS.
  
 10. [SATISFIED ??? SHOW AND LABEL PROPOSED PROPERTY
 LINES AT EACH END OF THE ALLEY ABANDONMENT] SHOW THE
 LIMITS OF THE PROPOSED ALLEY ABANDONMENT.
  
 11. SHOW HOW ALLEY GRADING WILL TRANSITION TO EXISTING
 GRADE.
  
 12. [SATISFIED] PROVIDE CROSS SECTIONS FROM CENTERLINE
 OF ROADWAY TO FACE OF BUILDING(S). LABEL STREET NAME
 AND SHOW RIGHT OF WAY LINE, SURFACE FEATURES AND
 SLOPES, BREAK POINTS, AND HORIZONTAL DISTANCES FROM
 RIGHT OF WAY LINE TO SURFACE FEATURES.
  
 13.[SATISFIED] PROVIDE SECTIONS AT ALL DRIVEWAYS FROM 5
 FEET FROM EDGE OF PAVEMENT TO 5 FEET PAST HIGH POINT OF
 DRIVEWAY (OR TRENCH DRAIN). SHOW RIGHT OF WAY LINE AND
 DISTANCE FROM R/W TO EP, BACK OF SIDEWALK, HIGH
 POINT/TRENCH DRAIN.
  
 14. [SATISFIED] SHOW EXISTING STORM PIPE ON PINE STREET
 WEST OF AND CONNECTING TO THE EXISTING STORM MANHOLE
 SOUTHEAST OF STRUCTURE ST-31.
  
 15. [PARTIALLY SATISFIED] LABEL EXISTING UTILITIES IN
 THE RIGHT OF WAY (PIPE SIZE, MATERIAL, ETC.)
  
 16. [SATISFIED] LABEL PROPOSED CURBS AND GUTTERS.
  
 17. [SATISFIED] PROVIDE PROPOSED FINISHED FLOOR
 ELEVATIONS ON THE PGD PLANS.
  
 18. [PARTIALLY SATISFIED ??? INCLUDE MILL AND RESURFACE
 HATCHING IN THE SHEET LEGENDS.] SHOW MILL AND
 RESURFACING LIMITS AND PAVEMENT MARKINGS WITHIN THESE
 LIMITS.
  
 19. [SATISFIED] WATER MAIN MAY BE IN CONFLICT WITH
 PROPOSED STRUCTURE ST-31.
  
 20. [SATISFIED] THERE APPEARS TO BE A LOW POINT IN THE
 EP IN FRONT OF THE DRIVEWAY TO BUTLER STREET OPPOSITE
 BROWARD AVE. HOW WILL THIS AREA IN FRONT OF THE
 DRIVEWAY DRAIN?
  
 21. [NOT SATISFIED] PROVIDE ADDITIONAL EXISTING GRADES
 ALONG THE EP OF N. FLAGLER DRIVE, NORTH OF THE PROPOSED
 DRIVEWAY.
  
 NEW COMMENTS (8/26/2022 SUBMITTAL)
  
 22. SECTION A-A
  A. BEGINNING OF DRIVEWAY SHOULD MEET EXISTING GRADE.
  B. VALLEY GUTTER MAY NOT BE NEEDED.
  C. CREATE A HIGH POINT IN THE DRIVEWAY AT THE BACK OF
 SIDEWALK AND ELIMINATE THE TRENCH DRAIN. ADD A CATCH
 BASIN ONTO THE 18 INCH STORM PIPE TO COLLECT RUNOFF
 WITHIN THE BUILDING.
  
 23. SECTION C-C
  A. MOVE SECTION ABOUT 20 FEET TO THE WEST TO FALL
 WITHIN THE LANDSCAPE AREA BETWEEN THE SIDEWALKS AND
 THROUGH THE SEATWALLS.
  B. FG LINE APPEARS TO BE SHIFTED TO THE RIGHT. IF NOT
 THEN ABOUT 5 FEET OF SIDEWALK CROSS SLOPE IS TOO STEEP.
  C. CONFIRM PROPOSED GRADE OF 6.01 (VS. 6.10 ON PGD
 PLAN).
  D. R/W DIMENSIONS ADD UP TO LESS THAN 37.5 FEET.
  E. THE FLOOR OF THE BUILDING INTERIOR APPEARS TO HAVE
 10% SLOPE.
  F. SHEET A0.08 SHOWS A DOOR OPENING TO THE CAF?? SPACE
 WHERE THE PGD PLAN SHOWS SPOT GRADES BETWEEN 8.03 FEET
 AND 6.34 FEET NAVD ADJACENT TO THE BUILDING. CAF?? FFE
 IS 9.00 FEET NAVD.
  
 24. SECTION D-D
  A. NOT SHOWN ON KEY MAP.
  B. BEGINNING OF DRIVEWAY SHOULD MEET EXISTING GRADE.
  
 25. SECTION F-F
  A. CREATE A HIGH POINT IN THE DRIVEWAY AT THE
 PROPERTY/RIGHT OF WAY LINE, CONVERT ST-29 TO A CATCH
 BASIN AND ELIMINATE THE TRENCH DRAIN. THIS WILL ALLOW
 ST-29 TO BE SMALLER THAN 7 FEET IN DIAMETER BY
 ELIMINATING THE SOUTH PIPE CONNECTION.
  B. R/W DIMENSIONS ADD UP TO LESS THAN 25 FEET.
  
 26. SECTION G-G
  A. DIMENSIONS DO NOT MATCH WHAT IS SHOWN ON SHEET
 C-400.
  B. SECTION SYMBOL ON KEY MAP SHOULD POINT TO THE WEST.
  C. WILL SIDEWALK HAVE A THICKENED EDGE? PROVIDE A
 DETAIL OF THE SIDEWALK IF SO.
  D. SHOW HEIGHT OF SITE WALL.
  E. CREATE A SWALE OR BERM ALONG THE PROPERTY LINE TO
 PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY.
  F. SHOW CURBING ADJACENT TO THE ISLAND AND IN-BOUND
 DRIVEWAY.
  
 27. SECTION H-H
  A. SHOW HEIGHT OF SITE WALLS.
  B. WHY CAN???T THE FRONT OF SIDEWALK NEAREST THE R/W
 MATCH EXISTING GRADE?
  C. CREATE SWALE BEHIND EAST SITE WALL TO PREVENT
 RUNOFF FROM FLOWING ONTO SIDEWALK.
  
 28. PROVIDE DETAIL SHOWING 18-INCH PIPE CONNECTION TO
 TRENCH DRAIN.
  
 29. SECTION G-G SHOWS THE DRIVEWAY SLOPING TO THE
 NORTH. THE TRENCH DRAIN ACROSS N. FLAGLER DRIVEWAY
 NEEDS TO EXTEND TO NORTH CURB LINE.
  
 30. CONSIDER ADDING TRENCH DRAIN ALONG NORTH CURB LINE
 WEST OF THE SIDEWALK CROSSING OF THE N. FLAGLER
 DRIVEWAY TO REDUCE THE AMOUNT OF RUNOFF FLOWING ACROSS
 THE SIDEWALK CROSSING.
  
 31. DRIVEWAY APRONS WITHIN THE RIGHT OF WAY SHOULD BE
 CONCRETE.
  
 32. CONSIDER MOVING SANITARY MANHOLE SS-05 OUT OF THE
 DRIVEWAY AND OUT OF THE SIDEWALK. COORDINATE WITH THE
 PUBLIC UTILITIES DEPARTMENT.
  
 33. REMOVE STRUCTURES ST-28 AND ST-34 OUT OF THE ALLEY
 R/W.
  
 34. SOUTH EDGE OF ALLEY NEEDS TO MEET EXISTING GRADE AT
 RIGHT OF WAY.
  
 35. WILL SIDEWALK AT DROPOFF AREA BE FLUSH WITH
 PAVEMENT AND/OR HAVE THICKENED EDGE?
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  