2022-08-06 10:51:29PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SHEET C600: FOR THE EASTERN TWO FIRE HYDRANTS ON PINE
 ST., SHOW CONNECTIONS TO WATER MAIN AND VERIFY THEY ARE
 FUNCTIONAL. THERE MAY BE A WATER MAIN RUNNING DOWN PINE
 ST; FOR THE WESTERN FIRE HYDRANT ON PINE ST, VERIFY IT
 EXISTS. RECENT PICTURES OF AREA SHOW NO FIRE HYDRANT
 THERE; SHOW WATER MAIN CONTINUATION SOUTH AT
 INTERSECTION OF FLAGLER AND PINE; LABEL WATER MAIN ON
 BUTLER ST WITH PIPE SIZE AND MATERIAL TYPE.
 -FOR THE FIVE EXISTING SEWER MANHOLES ON WESTERN SIDE
 OF BUTLER ST, SHOW ANY PIPING CONNECTING TO THEM AND
 PROVIDE INVERT ELEVATIONS.
 -WPB GIS SHOWS SEWER MAIN FLOWING SOUTH AT SS10. AT
 SS10 SHOW SEWER MAIN RUNNING SOUTH FROM MANHOLE AND
 PROVIDE ALL THREE INVERT ELEVATIONS; PROPOSED SEWER
 MAIN ON PINE ST IS 10 INCH, BUT A FEW BLOCKS SOUTH OF
 SS10 SEWER MAIN REDUCES TO 8 INCH SIZING PER WPB GIS.
 VERIFY WASTEWATER WILL FLOW ALRIGHT.
 -SHOW AND LABEL GREASE TRAPS ON CIVIL PLANS.
 -SHEET C602: SIGN POLE OVER WATER SERVICE. PLEASE
 PROVIDE CLEARANCE DISTANCE; CALLOUT LARGE WATER METER
 AND ADD WORDING ABOVE-GROUND ON LABEL IF OVER 2 INCHES;
 CONSIDER DUAL OR PARALLEL DOMESTIC BACKFLOW ASSEMBLIES
 TO REDUCE WATER OUTAGES DURING BACKFLOW MAINTENANCE;
 ADJUST FIRELINE POINT OF SERVICE VALVE SLIGHTLY NORTH
 INTO LANDSCAPING AND OUT OF PEDESTRIAN WALKWAY; LABEL
 WHAT EACH 2 INCH METER FEEDS OR ITS USE, SUCH AS
 IRRIGATION.
 -VERTICAL BACKFLOW ASSEMBLIES ARE NONSTANDARD. BACKFLOW
 ASSEMBLIES MUST BE USC APPROVED FOR THE ORIENTATION BY
 MAKE, MODEL, AND SIZE. THEY WOULD ALSO REQUIRE FURTHER
 ENGINEERING REVIEW AND APPROVAL.
 -PROPERTY OWNER WILL HAVE TO RECORD BACKFLOW COVENANT
 AS A CONDITION OF WATER SERVICE.
 -SHEET 601 AND 602: ADD THE DARK BLACK BOXES TO LEGEND.
 VERIFY THEY WILL NOT CONFLICT WITH THE CONTINUATION OF
 FIRE SERVICE PIPE.
 -SHEET 601: VERIFY AND SHOW LOCATIONS OF EXISTING SEWER
 LATERALS FOR 309 TO 325 PINE ST.
 -PROPOSED LOCATION OF SS03 APPEARS TO BE CONFLICTING
 WITH EXISTING METAL FENCE.
 -VERIFY 300 BUTLER ST. HAS AGREED TO GRANT UTILITY
 EASEMENT.
 -WPB UTILITY BILLING SHOWS EXISTING 4 INCH FIRELINE AT
 200 BUTLER. SHOW AND LABEL REMOVAL ON CIVIL PLANS.
 -ARE THE UTILITY POLES AND OVERHEAD UTILITY LINES ON
 NORTH SIDE OF ALLEY REMAINING?
 -SHOW PAVEMENT RESTORATION BOUNDARIES FOR UTILITY WORK
 IN PINE ST, FLAGLER DR, BUTLER, ALLEY, DIXIE HWY, AND
 300 BUTLER PARKING LOT.
 -SURVEY DOES NOT INCLUDE ALL AREAS OF PROPOSED UTILITY
 WORK.
 -COULD NOT LOCATE FDC. SHOW AND LABEL IF ANY ARE NEEDED
 OR REQUIRED. IF ADDING ANY ENSURE THAT THEY ARE
 ACCEPTABLE DISTANCES FROM FUNCTIONAL FIRE HYDRANTS.
 -ADD WATER DEMAND CALCULATIONS TO UTILITY PLANS.
 -SURVEY SHEET 4 OF 4 SAYS LAND EAST OF FLAGLER IS
 GOVERNMENT LOT. IS IT OWNED BY CITY OF WEST PALM BEACH?
 -ON CIVIL PLANS SHOW EXISTING PARKING SPOTS, BIKE LANE,
 AND MEDIAN STRIPING ON EAST SIDE OF FLAGLER DR.
 -SHEET L0101 SHOWS PROPOSED TREES CONFLICTING WITH
 UTILITIES. PROVIDE CLEARANCE DISTANCE.
 -LANDSCAPE PLANS DO NOT APPEAR TO BE ACCURATELY SHOWING
 LOCATIONS OF UTILITIES FROM CIVIL PLANS. FOR INSTANCE,
 THE LOCATIONS OF THE 2 INCH METERS AND BACKFLOW
 ASSEMBLIES ARE DIFFERENT. ENSURE ALL SETS OF PLANS HAVE
 THE SAME LOCATIONS.
 -WHY ARE THE ELECTRIC AND WATER LINES PROPOSED RUNNING
 ACROSS FLAGLER?
 -ADD UTILITY STANDARD DETAILS FOR SMALL BACKFLOW
 ASSEMBLY, FIRELINE BACKFLOW ASSEMBLY, LARGE BACKFLOW
 ASSEMBLY, AND LARGE ABOVE GROUND METER.
 -ENSURE ANY PROPOSED OUTSIDE FPL TRANSFORMER PADS ARE
 SHOWN AND LABELED.
 -WHAT IS HAPPENING TO THE 5 FOOT UTILITY EASEMENTS
 RUNNING THROUGH PROPERTY AS SHOWN ON THE SURVEY?
 -VERIFY IF THERE WILL BE ANY AUXILIARY WATER SUPPLIES
 SUCH AS WELLS CONNECTED TO THE PRIVATE FIRE SYSTEM.
 RESPECTFULLY,