| Plan Review Notes For Project Z22060032 |
| Project Number |
Z22060032 |
|
| Review Stop |
PU-CS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-11 16:34:19 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | | | | -CANNOT FIND GREASE TRAP ON PLANS. IF IT WILL BE | | | OUTSIDE SHOW IT ON CIVIL PLANS. | | | | | | -VERIFY METER SIZE IS SUFFICIENT FOR INCREASED WATER | | | DEMAND. | | | | | | -VERIFY FORCE MAIN SIZING IS SUFFICIENT FOR INCREASED | | | SEWER DEMAND FROM HOTEL LIFT STATION ALL THE WAY TO | | | OUTLET MANHOLE NEAR 45TH ST. | | | | | | -RECENTLY EOR SUGGESTED ALTERATION OF SIDEWALK NEAR | | | WATER METERS. IF CHANGE IS PROPOSED, SHOW ON | | | RESUBMITTAL. | | | | | | -UPDATE LANDSCAPING PLAN TO BETTER SHOW UTILITIES ON | | | SITE. VERIFY IF THERE IS ANY CONFLICT BETWEEN TREES AND | | | WASTEWATER INFRASTRUCTURE. | | | | | | -UPDATE OVERALL SITE PLAN TO SHOW NEW LOCATION OF LIFT | | | STATION AND ELIMINATION OF PROPERTY ENTRANCE NEAR THE | | | SOUTHWEST AREA OF PROPOSED GARAGE. | | | | | | -THIS WOULD AFFECT E20090024. |
| |