Plan Review Notes
Plan Review Notes For Project Z22060030
Project Number Z22060030
Review Stop STORM
Sequence Number 5
Notes
Date Text
2023-02-08 12:32:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 1/19/2023 PPRC SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS
 ARE NOT INCLUDED.
  
 10. [SATISFIED - EOR TO RESOLVE PRIOR TO ENGINEERING
 PERMIT SUBMITTAL.] CHECK THE PROPOSED ELEVATIONS AT THE
 BASE OF THE STEPS FOR THE UNITS ALONG 25TH STREET VS.
 THE EXISTING BACK OF SIDEWALK ELEVATION. SOME PROPOSED
 ELEVATIONS APPEAR TO BE BELOW THE BOW OR MORE THAN 1
 INCH ABOVE THE BOW.
  
 NEW COMMENTS (8/4/2022 SUBMITTAL):
  
 13. [SATISFIED ??? ALL STORM PIPES WITHIN THE R/W SHOWN
 TO BE 15-INCHES] JUSTIFY ALL OUTFALL PIPE DIAMETERS
 LARGER THAN 15 INCH. THIS INFORMATION CAN BE PROVIDED
 WITH ENGINEERING PERMIT SUBMITTAL.
  
 19. [PARTIALLY SATISFIED ??? NEED GRADES FOR THE
 CORNERS OF THE BULBOUT CREATED FOR THE ALLEY ACCESS
 EASEMENT.] PROVIDE GRADES AROUND THE NEW ALLEY ENTRANCE
 ON 24TH ST.
  
 20. [PARTIALLY SATISFIED - LABEL ALL EXISTING UTILITIES
 ON THE PAVING AND GRADING, THE DRAINAGE AND THE WATER
 AND WASTEWATER PLAN SHEETS. SHALL BE ADDRESSED FOR
 ENGINEERING PERMIT SUBMITTAL.] LABEL (SIZE AND
 MATERIAL) EXISTING UTILITIES IN THE RIGHT OF WAY.
  
 21. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS
 AND COORDINATE THE LANDSCAPING AND UTILITY PLANS.
  
 NEW COMMENTS (12/21/22 SUBMITTAL):
 22. [SATISFIED] REVIEW SPOT GRADE OF 16.40 FT NAVD AT
 NORTHEAST CORNER OF THE DEVELOPMENT. THIS GRADE IS ONE
 FOOT HIGHER THAN THE FFE. COMMENT CAN BE ADDRESSED AT
 ENGINEERING PERMIT SUBMITTAL.
  
 23. [NOT SATISFIED ??? SHALL BE ADDRESSED WITH THE
 ENGINEERING PERMIT SUBMITTAL] REVIEW EXISTING SPOT
 GRADES ALONG THE NORTH CURB LINE OF 24TH ST, WEST OF
 THE ALLEY DRIVEWAY. THERE IS A 2.5+ FEET DROP ACROSS
 THE PARKING SPACE (15.71 TO 13.08 FT NAVD).
  
 24. [NOT SATISFIED ??? SHALL BE ADDRESSED WITH THE
 ENGINEERING PERMIT SUBMITTAL] PROPOSED ALLEY DRIVEWAY
 BULBOUT WILL INTERRUPT/BLOCK THE DRAINAGE FLOW WEST OF
 THE DRIVEWAY.
  
 25. [SATISFIED] SECTION A FOR THE ALLEY R/W (SHED
 SECTION) DOES NOT MATCH THE GRADING PLAN FOR THE ALLEY
 (INVERTED CROWN) OR MATCH THE PROPOSED SPOT GRADES.
  
 26. PARTIALLY SATISFIED. CAN BE ADDRESSED WITH THE
 ENGINEERING PERMIT SUBMITTAL] SECTION C SHOWS THE ALLEY
 PAVEMENT SLOPING TO THE RIGHT (OR NORTH). THE GRADING
 PLAN INDICATES THE ALLEY WILL SLOPE TO THE SOUTH.
  
 27. [SATISFIED] SECTION E - PROVIDE STEEPER CROSS SLOPE
 (0.5% MIN. ) FOR 10 FT WIDE SIDEWALK TO PROMOTE
 DRAINAGE. THE SPOT GRADES WILL CREATE A 0.1% CROSS
 SLOPE. INDICATE WHAT THE 15.62 SPOT GRADE IS FOR. THESE
 COMMENTS CAN BE ADDRESSED DURING ENGINEERING PERMIT
 SUBMITTAL.
  
 28. SECTION F -
 A. [PARTIALLY SATISFIED ??? CONFIRM THE DISTANCE IS 10
 INCHES OR 10 FEET] LABEL THE R/W LINE AND THE DISTANCE
 FROM THE BACK OF CURB.
 B. [SATISFIED] SECTION ARROWS FACING THE WRONG
 DIRECTION.
 C. [SATISFIED ??? NOTE THE BUILDING CODE REQUIRES THE
 SURFACE ADJACENT TO THE BUILDING TO SLOPE AWAY FROM THE
 BUILDING] IS THE BERM NECESSARY ALONG THE BUILDING.
  
 29. [NOT SATISFIED ??? SHALL BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL] ADD THE FOLLOWING LINE
 TYPES TO THE SHEET LEGEND: H2O, ELEC, FO, SAN AND ANY
 OTHER LINETYPES THAT APPEAR ON THE PLANS. THIS CAN BE
 ADDRESSED DURING ENGINEERING PERMIT SUBMITTAL.
  
 CONDITIONS FOR SITE PLAN APPROVAL:
 1. DEVELOPER TO BE RESPONSIBLE TO MAINTAIN THE DRAINAGE
 SYSTEM IN THE ALLEY EASEMENT.
  
 2. GRADING OF PUBLIC ALLEY IS TO BLEND IN WITH THE
 ADJOINING PROPERTIES WITHOUT ADDING ADDITIONAL RUNOFF
 TO THE ADJOINING PROPERTIES OR PREVENTING EXISTING
 RUNOFF FROM THE PROPERTIES. ANY DRAINAGE INFRASTRUCTURE
 INSTALLED TO SATISFY THIS REQUIREMENT SHALL BE THE
 RESPONSIBILITY OF THE DEVELOPER TO MAINTAIN. AVOID THE
 INSTALLATION OF RAISED CURBING, WHICH WILL NARROW THE
 AVAILABLE TRAVEL WIDTH IN THE ALLEY.
  
 3. CURB RAMPS TO BE RE-CONSTRUCTED TO MEET CURRENT ADA
 STANDARDS IF THE ASPHALT ADJACENT TO THE RAMP IS
 MODIFIED IN ANY WAY.
  
 4. ALLEY ACCESS AND UTILITY EASEMENT LINES TO BE SHOWN
 ON ALL OF THE ENGINEERING PLAN SHEETS.
  
 5. PROPOSED DRAINAGE SYSTEM AND IMPROVEMENTS WITHIN THE
 24TH STREET RIGHT OF WAY TO BE APPROVED BY FDOT. THE
 DISRUPTION OF THE GUTTER FLOW BY THE ALLEY EASEMENT
 DRIVEWAY BULBOUT IS TO BE RECTIFIED.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  