Plan Review Notes
Plan Review Notes For Project Z22060030
Project Number Z22060030
Review Stop STORM
Sequence Number 4
Notes
Date Text
2023-01-18 16:01:08THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/21/22 PPRC SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS
 ARE NOT INCLUDED.
  
 1. [SATISFIED] CONVERSION EQUATION TO NGVD1929 NOT
 LISTED. 12/8/22 UPDATED COMMENT - THE SURVEY LISTS THE
 CONVERSION FACTOR AS 1.50 FT. THE CIVIL PLANS LIST THE
 CONVERSION FACTOR AS 1.522 FEET. THE CONVERSION
 EQUATION SHOULD MATCH ON THESE DOCUMENTS.
  
 6. [SATISFIED] PROVIDE CROSS SECTIONS FROM FACE OF
 BUILDING TO CENTERLINE OF RIGHTS OF WAY FOR 24TH
 STREET, 25TH STREET AND SPRUCE AVE. SHOW RIGHT OF WAY,
 OFFSET DISTANCES, SURFACE FEATURES, GENERAL SURFACE
 SLOPES WITH MAX. ALLOWED PERCENTAGES, BREAK POINTS,
 ETC.
  
 10. [NOT SATISFIED ??? EOR TO RESOLVE PRIOR TO
 ENGINEERING PERMIT SUBMITTAL.] CHECK THE PROPOSED
 ELEVATIONS AT THE BASE OF THE STEPS FOR THE UNITS ALONG
 25TH STREET VS. THE EXISTING BACK OF SIDEWALK
 ELEVATION. SOME PROPOSED ELEVATIONS APPEAR TO BE BELOW
 THE BOW OR MORE THAN 1 INCH ABOVE THE BOW.
  
 NEW COMMENTS (8/4/2022 SUBMITTAL):
  
 13. [NOT SATISFIED] JUSTIFY ALL OUTFALL PIPE DIAMETERS
 LARGER THAN 15 INCH. THIS INFORMATION CAN BE PROVIDED
 WITH ENGINEERING PERMIT SUBMITTAL.
  
  
 16. [SATISFIED] PROVIDE A CROSS SECTION FOR THE ALLEY
 ENTRANCE FROM THE CENTERLINE OF 24TH STREET TO 5 FEET
 NORTH OF THE NORTH RIGHT OF WAY OF 24TH ST. SHOW GRADE
 BREAKS, SURFACE MATERIALS, RIGHT OF WAY LINE, RIGHT OF
 WAY NAME, DIMENSIONS FROM RIGHT OF WAY TO GRADE BREAKS.
  
 17. [SATISFIED] SHOW AND CALLOUT NEW CURBING ON 24TH
 STREET AND THE REMOVAL OF THE EXISTING CURBING FOR THE
 PROPOSED ALLEY DRIVEWAY AND LANDSCAPE ISLANDS.
  
 19. [NOT SATISFIED] PROVIDE GRADES AROUND THE NEW ALLEY
 ENTRANCE ON 24TH ST.
  
 20. [PARTIALLY SATISFIED - LABEL ALL EXISTING UTILITIES
 ON THE PAVING AND GRADING, THE DRAINAGE AND THE WATER
 AND WASTEWATER PLAN SHEETS.] LABEL (SIZE AND MATERIAL)
 EXISTING UTILITIES IN THE RIGHT OF WAY.
  
 21. [NOT SATISFIED - ONLY STRUCTURES ARE SHOWN, NO
 PIPING.] SHOW UTILITIES ON THE LANDSCAPE PLANS AND
 COORDINATE THE LANDSCAPING AND UTILITY PLANS.
  
 NEW COMMENTS (12/21/22 SUBMITTAL):
 22. REVIEW SPOT GRADE OF 16.40 FT NAVD AT NORTHEAST
 CORNER OF THE DEVELOPMENT. THIS GRADE IS ONE FOOT
 HIGHER THAN THE FFE. COMMENT CAN BE ADDRESSED AT
 ENGINEERING PERMIT SUBMITTAL.
  
 23. REVIEW EXISTING SPOT GRADES ALONG THE NORTH CURB
 LINE OF 24TH ST, WEST OF THE ALLEY DRIVEWAY. THERE IS A
 2.5+ FEET DROP ACROSS THE PARKING SPACE (15.71 TO 13.08
 FT NAVD).
  
 24. PROPOSED ALLEY DRIVEWAY BULBOUT WILL
 INTERRUPT/BLOCK THE DRAINAGE FLOW WEST OF THE DRIVEWAY.
  
 25. SECTION A FOR THE ALLEY R/W (SHED SECTION) DOES NOT
 MATCH THE GRADING PLAN FOR THE ALLEY (INVERTED CROWN)
 OR MATCH THE PROPOSED SPOT GRADES.
  
 26. SECTION C SHOWS THE ALLEY PAVEMENT SLOPING TO THE
 RIGHT (OR NORTH). THE GRADING PLAN INDICATES THE ALLEY
 WILL SLOPE TO THE SOUTH.
  
 27. SECTION E ??? PROVIDE STEEPER CROSS SLOPE (0.5%
 MIN. ) FOR 10 FT WIDE SIDEWALK TO PROMOTE DRAINAGE. THE
 SPOT GRADES WILL CREATE A 0.1% CROSS SLOPE. INDICATE
 WHAT THE 15.62 SPOT GRADE IS FOR. THESE COMMENTS CAN BE
 ADDRESSED DURING ENGINEERING PERMIT SUBMITTAL.
  
 28. SECTION F ???
 A. LABEL THE R/W LINE AND THE DISTANCE FROM THE BACK OF
 CURB.
 B. SECTION ARROWS FACING THE WRONG DIRECTION.
 C. IS THE BREM NECESSARY ALONG THE BUILDING.
  
 29. ADD THE FOLLOWING LINE TYPES TO THE SHEET LEGEND:
 H2O, ELEC, FO, SAN AND ANY OTHER LINETYPES THAT APPEAR
 ON THE PLANS. THIS CAN BE ADDRESSED DURING ENGINEERING
 PERMIT SUBMITTAL.
  
 CONDITIONS FOR SITE PLAN APPROVAL:
 1. DEVELOPER TO BE RESPONSIBLE TO MAINTAIN THE DRAINAGE
 SYSTEM IN THE ALLEY EASEMENT.
  
 2. GRADING OF PUBLIC ALLEY IS TO BLEND IN WITH THE
 ADJOINING PROPERTIES WITHOUT ADDING ADDITIONAL RUNOFF
 TO THE ADJOINING PROPERTIES.
  
 3. CURB RAMPS TO MEET CURRENT ADA STANDARDS IF THE
 ASPHALT ADJACENT TO THE RAMP IS MODIFIED IN ANY WAY.
  
 4. ALLEY EASEMENT LINES TO BE SHOWN ON ALL OF THE
 ENGINEERING PLAN SHEETS.
  
 5. 24TH STREET DRAINAGE SYSTEM TO BE DESIGNED TO BE
 APPROVED BY FDOT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  