2023-01-31 10:01:02APPROVAL IS CONDITIONAL ON THE FOLLOWING BEING
 ADDRESSED DURING ENGINEERING REVIEW
 -PREVIOUS COMMENTS REGARDING CLEANOUTS NOT FULLY
 ADDRESSED. CLEANOUT SIZES HAVE NOT BEEN SPECIFIED AND
 THE PROPOSED CLEANOUT ALONG PROPERTY LINE ON SOUTHEAST
 PART OF PROPERTY WILL REQUIRE AN EASEMENT IN ITS
 CURRENT LOCATION. REFER TO CITY DETAIL GS-6 FOR FURTHER
 CLARIFICATION
 -PROFILES WILL BE REQUIRED FOR ENGINEERING SUBMITTAL
 -EXISTING 16"X16"X8" TEE DEPICTED ON PLANS NOT SHOWN IN
 GIS. VERIFY THE EXISTING VALVE PROPOSED FOR CONNECTION,
 OR OTHER MEANS OF CONNECTION TO 16" WATER MAIN WILL
 NEED TO BE MADE.
 -PROPOSED 4" REMOVAL INCLUDES PORTION OF EXISTING 8"
 WATER MAIN, PROPOSED PLUG WOULD BE INTO EXISTING 8"
 GATE VALVE.
 -INVERTS FOR NORTH AND SOUTH STILL SHOWN ON SANITARY
 MANHOLE 1 DESPITE NO EXISTING PIPE RUNNING ALONG SPRUCE
  