Notes
Date Text
2023-01-17 10:44:07-DEMOLTION SHEET DOES NOT REFLECT REMOVAL OF EXISTING
 WATER AND SEWER MAINS ON SITE
 -CLEANOUT MUST BE LOCATED CLOSE TO PROPERTY LINE TO BE
 CONSIDERED "POINT OF SERVICE" (WTH EASEMENT AS NEEDED)
 -CONFIRM EXISTENCE OF SEWER MAIN RUNNING NORTH/SOUTH ON
 SPRUCE (RECORDS DON'T SHOW RUN THAT IS SHOW ON PLANS)
 -POINTS OF SERVICE FOR WATER AND SEWER THAT ARE INSIDE
 OF PROPERTY LINE WILL REQUIRE AN EASEMENT
 -MEANS OF CONNECTION FOR SANITARY SEEWER LATERALS NEED
 TO BE SPECIFIED
 -SPECIFY SIZES OF CLEANOUTS
  