| Plan Review Notes For Project Z22060030 |
| Project Number |
Z22060030 |
|
| Review Stop |
PU |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-01-17 10:44:07 | -DEMOLTION SHEET DOES NOT REFLECT REMOVAL OF EXISTING | | | WATER AND SEWER MAINS ON SITE | | | -CLEANOUT MUST BE LOCATED CLOSE TO PROPERTY LINE TO BE | | | CONSIDERED "POINT OF SERVICE" (WTH EASEMENT AS NEEDED) | | | -CONFIRM EXISTENCE OF SEWER MAIN RUNNING NORTH/SOUTH ON | | | SPRUCE (RECORDS DON'T SHOW RUN THAT IS SHOW ON PLANS) | | | -POINTS OF SERVICE FOR WATER AND SEWER THAT ARE INSIDE | | | OF PROPERTY LINE WILL REQUIRE AN EASEMENT | | | -MEANS OF CONNECTION FOR SANITARY SEEWER LATERALS NEED | | | TO BE SPECIFIED | | | -SPECIFY SIZES OF CLEANOUTS | | | | | | RICKY ELIZONDO | | | [email protected] | | | |
| |