| 2022-12-05 11:05:15 | -SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. |
| | -PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. (DENOTE |
| | THE LEGEND) |
| | -PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH |
| | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE |
| | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, |
| | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO |
| | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, |
| | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, |
| | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT |
| | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF |
| | SANITARY SEWER LINES. |
| | -DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN |
| | VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | -PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED |
| | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, |
| | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION |
| | FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN |
| | THE RIGHT-OF-WAY. |
| | -PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE |
| | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND |
| | MATERIAL LOCATED IN THE RIGHT-OF-WAY. |
| | -SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY |
| | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT |
| | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING |
| | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, |
| | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS |
| | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 |
| | FOR WATER. |
| | -PROVIDE FIRE FLOW TEST DATA. |
| | -PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG |
| | ENTIRE PROJECT FRONTAGE WHERE CONNECTION IS PROPOSED |
| | (CONDITION OF SITE PLAN APPROVAL). |
| | -CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | -WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL |
| | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY |
| | PROPOSED LENGTH IN FEET. |
| | -CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY SEWER |
| | ARE REQUIRED. |
| | -PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE |
| | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. |
| | -ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT |
| | STATION NUMBER. (AREA SERVES LS 23) |
| | -LABEL WATER LINES AS PRIVATE WHERE APPLICABLE |
| | -PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN |
| | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. |
| | -DENOTE POINTS OF SERVICE FOR BOTH WATER AND SEWER |
| | -EXISTING MANHOLES THAT ARE PROPOSED TO HAVE NEW |
| | CONNECTIONS WILL NEED TO BE REHABBED |
| | -NO DEMOLITION PLAN PROVIDED |
| | -CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE NOTE |
| | USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA |
| | -IF WATER LINES ARE BEING REPLACED IN ROW, SHOW |
| | ADJACENT PARCEL ADDRESSES. |
| |