| Date |
Text |
| 2022-07-11 14:13:27 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: |
| | |
| | -WHAT IS HAPPENING TO EXISTING UTILITY POLES AND |
| | OVERHEAD WIRES ALONG ALLEYWAY? |
| | |
| | -WPB GIS SAYS WATER MAIN IS TRANSITE AROUND AREA OF |
| | PROPOSED ELIMINATION. |
| | |
| | -THERE ARE EXISTING CITY UTILITIES NEAR ALLEY. |
| | APPLICANT MAY NEED TO RELOCATE THE UTILITIES AS |
| | REQUESTED BY CITY. |
| | |
| | -AT EAST SIDE OF ALLEY THERE IS A CITY STREET LIGHTING |
| | FEED AND MAY BE A POWER SUPPLY FOR CITY IRRIGATION. |
| | APPLICANT NEEDS SEPARATE APPROVAL FROM CITY FOR ANY |
| | CHANGES TO THOSE. |
| | |
| | -ON CIVIL PLANS PLEASE CLEARLY SHOW NEIGHBORING EDGES |
| | OF BUILDINGS ADJACENT ALLEY AND ALSO SHOW NEIGHBORING |
| | PARKING LOTS AND DRIVEWAYS CONNECTED TO ALLEY. |
| | |
| | -SHOW ALL EXISTING WATER SERVICES AROUND AREA OF WORK |
| | ON CIVIL PLANS. SOME EXISTING WATER SERVICES MAY NEED |
| | TO BE REMOVED OR RELOCATED AS DIRECTED BY CITY OR EOR. |
| | |
| | -IS A SEPARATE METERED IRRIGATION WATER SERVICE NEEDED? |
| | |
| | -BROADWAY MANHOLE SAYS WILL BE REMOVED BUT THERE ARE |
| | ADDITIONAL INVERTS. PLEASE CONFIRM IF THERE ARE OTHER |
| | SECTIONS OF PIPE CONNECTED AND IF REMOVAL WITH CAUSE |
| | PROBLEM. |
| | |
| | -SHOW ALL SEWER LATERAL CLEANOUTS. |
| | |
| | -DOMESTIC RP BACKFLOW ASSEMBLY IS NOT SHOWN. SHOULD BE |
| | OUTSIDE OF BUILDING. CONSIDER PUTTING IT IN LINE WITH |
| | METER EAST WEST. |
| | |
| | -CONSIDER PARALLEL/DUAL BACKFLOW ASSEMBLIES ON DOMESTIC |
| | WATER SERVICE TO MINIMIZE WATER OUTAGES DURING BACKFLOW |
| | MAINTENANCE. |
| | |
| | -SHOW UTILITY EASEMENT FOR DOMESTIC WATER METER AND |
| | SERVICE ON PRIVATE PROPERTY. |
| | |
| | -TWO PARKING SPOTS AND AN EXISTING TREE LOOK TO BE |
| | DISTURBED BY PROPOSED ALLEY CONNECTION. PLEASE CONTACT |
| | CITY PLANNING AND PARKING REPRESENTATIVES TO RESOLVE. |
| | |
| | -PROVIDE SEPARATE LANDSCAPING PLAN SHEET SHOWING |
| | UTILITIES. ENSURE THERE ARE NO CONFLICTS BETWEEN TREES |
| | AND UTILITIES. |
| | |
| | -PLEASE RELOCATE FIRELINE POINT OF SERVICE VALVE |
| | SLIGHTLY SOUTH IN LINE WITH THE METER VALVES. |
| | |
| | -PROPERTY OWNER WILL BE REQUIRED TO RECORD BACKFLOW |
| | COVENANT AS A CONDITION OF FIRELINE WATER SERVICE. |
| | |
| | -EXISTING WATER MAIN STUB AND VALVE ON 24TH ST MAY BE |
| | SHOWN AT WRONG LOCATION ON CIVIL PLAN. THAT MAY AFFECT |
| | PROPOSED LOCATIONS OF UTILITIES. |
| | |
| | -APPLICANT MUST COMPLY WITH ALL CITY WPB UTILITIES |
| | BILLING REQUIREMENTS. |
| | |
| | -EAST SIDE OF ALLEY CONNECTION ON 24TH ST LOOKS TO HAVE |
| | A RAMP. DOES THE WEST SIDE NEED ELEVATION TRANSITION |
| | ALSO? |
| | |
| | -IS THE NEW ALLEY ACCESS PROPOSED TO BE CITY RIGHT OF |
| | WAY OR PRIVATE PROPERTY WITH ACCESS EASEMENT? |
| | |
| | -PLEASE CLEARLY SHOW AND LABEL PROPERTY LINES ON CIVIL |
| | PLANS. |
| | |
| | -CLEARLY SHOW AND LABEL ANY PROPOSED TRANSFORMERS AND |
| | OUTSIDE GREASE TRAPS ON CIVIL PLANS. |
| |
Print |