| 2022-07-13 20:37:06 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY |
| | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER |
| | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE |
| | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE |
| | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF |
| | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION |
| | DISTANCE. |
| | |
| | 3. LOCATION OF ACCESSIBLE PARKING SPACES. SITE PLAN |
| | SHEET A1.0 SHOWS 3 ACCESSIBLE PARKING SPACES ON LEVEL 1 |
| | BUT THERE ARE REGULAR PARKING SPACES THAT ARE CLOSER TO |
| | THE BUILDING LOBBY, ELEVATORS, AND RETAIL SPACE, THAN |
| | THE 3 ACCESSIBLE PARKING SPACES ARE. PER SECTION 208.3 |
| | OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING |
| | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE |
| | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 4. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 5. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC |
| | VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1 |
| | IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE |
| | REQUIREMENTS. |
| | |
| | 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 7. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 9. GREASE INTERCEPTOR. IF THE RETAIL SPACE IS TO BE A |
| | REATAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR |
| | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, |
| | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, |
| | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR |
| | BY EMAIL: [email protected] |
| | |
| | 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 11. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. |
| | |
| | 12. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 13. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION |
| | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, |
| | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT |
| | (561) 805 6659, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |