Plan Review Notes
Plan Review Notes For Project Z22060027
Project Number Z22060027
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-09-29 16:16:29THE FOLLOWING COMMENT IS FROM THE REVIEW OF THE
 9/14/2022 RRESUBMITTAL:
  
 1. THE PARK DRAINAGE SYSTEM DISCAHRGES INTO THE GAINES
 PARK CANAL WHICH FLOWS INTO THE CARVER CANAL. BOTH THE
 CARVER CANAL AND GAINES PARK CANAL ARE AT THEIR MAXIMUM
 CAPACITY FOR THE 25-YEAR 1-DAY DESIGN STORM. ANY
 ADDITIONAL RUNOFF VOLUME FOR THIS DESIGN STORM,
 GENERATED BY THIS PROJECT, WILL NEED TO BE STORED
 ONSITE.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  