| Plan Review Notes For Project Z22060027 |
| Project Number |
Z22060027 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-09-20 08:11:38 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -SHEET UT1: IS LEADER LINE FOR PROPOSED FIRE SERVICE | | | POINTED CORRECTLY? | | | -EXISTING WATER MAIN INFRASTRUCTURE DOES NOT APPEAR TO | | | BE ABLE TO FACILITATE AN ADDITIONAL LARGE DIAMETER FIRE | | | SERVICE. THE NEARBY WATER MAIN IS SHOWING AS 6 INCH AND | | | IS NOT LOOPED PER WPB GIS. THERE IS ALREADY A 6 INCH | | | FIRE SERVICE, MULTIPLE METERS, AND A COUPLE FIRE | | | HYDRANTS, AS WELL AS ADDITIONAL PROPOSED METERS. | | | -SHEET UT2: SHOW ANY EXISTING OR PROPOSED HARDSCAPE | | | NEAR PROPOSED 1.5 INCH METER AND BACKFLOW. NEED | | | VERIFICATION THAT METER AND BACKFLOW WILL BE IN | | | LANDSCAPE INSTEAD OF HARDSCAPE AND NOT IN PEDESTRIAN | | | TRAFFIC. | | | -COULD NOT FIND ANY FDC ON UT1. SHOW AND LABEL IF ANY | | | ARE NEEDED OR REQUIRED. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
| |