| 2022-07-08 15:29:25 | -ON UTILITY PLAN UT1: SHOW AND LABEL WASTEWATER PUMP |
| | STATION NO. 29 |
| | -ON UTILITY PLANS: SHOW AND LABEL ALL EXISTING WATER |
| | SERVICES LINES, WATER METERS, WATER METER BOXES, SEWER |
| | LATERAL CLEANOUTS, MANHOLES, AND BACKFLOW ASSEMBLIES AS |
| | SOME ARE MISSING. |
| | -ON SHEET UT1 NEAR NE AREA OF BUILDING THERE IS A DDCV |
| | LABELED. THE 3 INCH BACKFLOW ASSEMBLY IS NOT A DDCV |
| | TYPE AND APPEARS TO BE A DOMESTIC WATER RP CONNECTED TO |
| | 2 INCH METER ADJACENT. NOTES IN SYSTEM SAY THE BACKFLOW |
| | VALVE IS TURNED OFF AND IN DISREPAIR. PLAN DESIGNER |
| | NEEDS TO INVESTIGATE FURTHER WHAT IT CURRENTLY SERVES |
| | AND IF IT IS NEEDED. |
| | -CONSIDER REPLACING ANY NON LEAD-FREE BACKFLOW |
| | ASSEMBLIES FOR WATER SERVICES THAT WILL BE USED FOR |
| | FOOD SERVICE OR DRINKING FOUNTAINS. |
| | -THERE IS FIRELINE DDCV NOT LABELED ON UT1 NEAR |
| | SOUTHWEST AREA OF SHEET UT1. IT ALSO HAS A LEAKING OSY |
| | VALVE THAT NEEDS REPAIR. |
| | -LABEL FIRE HYDRANTS AND ADD THE SYMBOL TO LEGEND. |
| | THERE IS A FIRE HYDRANT THAT IS NOT SHOWN ON UT1 NEAR |
| | THE SOUTHWEST DDCV. PLEASE SHOW AND LABEL ON UT1. CAN |
| | EXPAND AREA OR ADD MATCHLINE AND SEPARATE SHEET IF |
| | NEEDED. |
| | -VERIFY EXISTING PUMPING STATION AND FORCE MAIN ARE |
| | SUFFICIENT FOR ANY INCREASED SEWER DEMAND. |
| | -SHEET UT1: FOR THE SEWER LATERALS THAT ARE BEING |
| | REMOVED, IS THE SEWER PLUMBING BEING REROUTED INSIDE |
| | THE BUILDING TO THE NORTHEAST END OF THE BUILDING? |
| | -REVIEW THE CALLOUTS, LABELS, AND LEADER LINES FOR THE |
| | SANITARY SEWER WORK NEAR NORTHEAST AREA OF UT1. THEY |
| | MAY BE POINTED OR LABELED INCORRECTLY. |
| | -VERIFY EXISTING METERED WATER SERVICES WILL BE |
| | SUFFICIENT FOR ANY INCREASED WATER DEMAND. |
| | -IF THERE ARE ANY HOSE BIBS FOR PUMP STATION |
| | MAINTENANCE, RECOMMEND VERIFYING THEY HAVE ADEQUATE |
| | BACKFLOW PROTECTION. |
| | -SHEET UT2: ADD SIZING OF PROPOSED METER; ADD SIZING OF |
| | PROPOSED BACKFLOW ASSEMBLY; ADD RP TO LABEL OF PROPOSED |
| | BACKFLOW ASSEMBLY. SHOW HARDSCAPE NEAR PROPOSED METER |
| | AND BACKFLOW ASSEMBLY AND ENSURE LOCATION OF METER AND |
| | BACKFLOW WILL BE IN LANDSCAPING; SHOW EXISTING LARGE |
| | UTILITY BOX BETWEEN WATER FOUNTAIN AND EXISTING |
| | BACKFLOW ASSEMBLY FOR COURTS; SHOW EXISTING WATER LINES |
| | FOR WATER FOUNTAIN AND TENNIS COURT BACKFLOW ASSEMBLY |
| | AND WHAT IS HAPPENING TO THEM. ALSO ENSURE THOSE WATER |
| | LINES ARE DOWNSTREAM OF A WATER METER. |
| | -SHEET UT3: ENSURE ALL SYMBOLS AND ABBREVIATIONS ARE ON |
| | SHEET LEGEND. |
| | -CANNOT FIND DEMO PLAN SHEET. PLEASE ADD TO PLAN SET. |
| | -UT1 DOES NOT SHOW SIZE OF EXISTING GAS SERVICE NEAR |
| | SOUTH SIDE. IS IT SUFFICIENT? |
| | -SHEET UT2: SHOW AND LABEL 42 INCH FORCE MAIN. |
| | -SHOW RAISED ELEVATION AREA NEAR POOL ON PGD1. |
| | -ADD WPB STANDARD DETAILS TO CIVIL DETAILS SHEETS FOR: |
| | FIRE HYDRANT, SMALL METERED WATER SERVICE, FIRELINE |
| | DETECTOR BACKFLOW, SMALL BACKFLOW ASSEMBLY, LARGE |
| | BACKFLOW ASSEMBLY. |
| |