Plan Review Notes
Plan Review Notes For Project Z22050025
Project Number Z22050025
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-09-16 13:46:43PER TRACY WARD:
 COMMENTS FROM THE 8/22/22 SUBMITTAL:
 1. GRADING (9.00 FT NAVD) OF SWALE AREA ADJACENT TO
 STRUCTURE YD-21 DOES NOT MATCH SECTION I-I (9.85 FT
 NAVD). REVISE RIM ELEV. OF YD-21.
 2. CHECK SPOT GRADES (7.69, 7.77) FOR CONNECTOR
 SIDEWALK TO THE NORTHEAST OF STRUCTURE ST-3.
 3. CHECK SPOT GRADES (10.86, 10.79) OF WEST END OF
 CURVED SIDEWALK. THEY ARE OPPOSITE DIRECTION OF WHAT
 SECTION I-I (AND PLAN SHEET FLOW ARROW) SHOWS THE
 SIDEWALK SHOULD BE SLOPING.
 4. FLAT SIDEWALK CROSS SLOPE (11.23, 11.23) SOUTHWEST
 OF STRUCTURE YD-1. DOES THE SIDEWALK (AT LEAST THE BACK
 OF WALK) SLOPE UP TO THE NORTH AND TO THE SOUTH FROM
 THIS POINT?
 5. SHEET C-502:
 A. CHECK EAST PIPE SIZE (12 INCH RCP) FOR STRUCTURE
 S-10. DOESN'T MATCH SHEET C-501 (EXIST. 15??? RCP).
 B. LIST THE WEIR ELEVATION FOR THE CONTROL STRUCTURES.
 C. INDICATE WHICH STRUCTURES SHOULD HAVE PRBS' AND FOR
 WHICH INVERT.
 D. LABEL ST-3 (AND ANY OTHER STRUCTURES WITH WEIRS) AS
 A CONTROL STRUCTURE.
  
  