2022-06-09 11:54:35CALL OUT THE EXISTING 4? CAS AND 3? AC WM ON CURRIE
 CRESCENT. ARE THESE GOING TO BE REMOVED DURING THE
 FLAGLER FORTE DEMO? IF SO PLEASE NOTE.
  - FOR ENGINEERING SUBMITTAL PROVIDE PROFILE AND
 VERTICAL CLEARANCES BETWEEN WATER, SEWER AND STORM
 LINES PER CITY OF WEST PALM BEACH STANDARD DETAIL GN-2
 SERIES, AT ALL UTILITY CROSSINGS. SHOW EXISTING
 UNDERGROUND UTILITIES ON THE PROFILE. THE PROFILE
 SHOULD SHOW PROPOSED PIPE FROM TIE-IN AT THE MAIN TO
 POINT OF SERVICE.
  - SHOW STATIONING AND HORIZONTAL SEPARATION CLEARANCE
 BETWEEN PROPOSED UTILITIES AND EXISTING UTILITIES
 AND/OR BASELINE.
  -ADD NOTE THIS IS WITHIN LS 40 SERVICE BOUNDARY.
  -ADD FIRE FLOW CALCS. PROVIDE THE MINIMUM REQUIRED
 FLOW AS WELL.
  