| 2022-09-07 16:01:29 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | NO COMMENTS ON PROPOSED AMENDMENTS TO THE PLANS. THE |
| | FOLLOWING ARE THE SAME INFORMATIONAL COMMENTS THAT WERE |
| | PROVIDED WHEN THE PREVIOUS REVIEW WAS PASSED: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. |
| | |
| | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS |
| | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT |
| | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH |
| | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, |
| | OR BY EMAIL: [email protected] |
| | |
| | 3. FLOOD ZONE. PROVISO/CONDITION: AS STATED IN THEIR |
| | PPRC RESPONSE LETTER DATED 9/13/2021 THE DESIGN TEAM |
| | HAS ADVISED THAT IT WILL SEEK ISSUANCE OF A LETTER OF |
| | MAP REVISION BASED ON FILL LOMR-F BY FEMA IN ORDER TO |
| | ADDRESS THE COMMENT REGARDING THE PROPOSED FINISHED |
| | FLOOR LEVEL BEING EL 9.0 FT NAVD INSTEAD OF THE EL 10.0 |
| | FT NAVD THAT WOULD BE REQUIRED TO MEET THE BASE FLOOD |
| | ELEVATION PLUS 2.0 FT FREEBOARD. CONDITION: EITHER THE |
| | LOMR-F MUST BE SUBMITTED TO THE BUILDING DIVISION PRIOR |
| | TO BUILDING PERMIT ISSUANCE, OR THE FINISHED FLOOR |
| | LEVEL BEING RAISED TO EL 10.0 FT NAVD. |
| | |
| | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE |
| | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE |
| | AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING |
| | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) |
| | 805-6692, OR BY EMAIL: [email protected] |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND |
| | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF |
| | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL |
| | NEIGHBORING PROPERTIES. |
| | |
| | 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER |
| | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, |
| | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE |
| | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF |
| | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION |
| | THAT MAY AFFECT THE USE OF THEIR PROPERTY. |
| | |
| | 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT |
| | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL |
| | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION |
| | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, |
| | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT |
| | (561) 805 6659, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |