| Notes |
| Date |
Text |
| 2022-06-07 16:10:08 | -AT FORMAL ENGINEERING SUBMITTAL: IDENTIFY GAS LINE | | | NEAR PROPOSED FIRE HYDRANT MORE CLEARLY ON UTILITY PLAN | | | SHEET C600; LABEL IRRIGATION WATER SERVICE LINE WITH | | | PIPE SIZE AND MATERIAL TYPE; ADD SCALE MEASUREMENT ICON | | | TO WATER METER DETAIL ON SHEET C600; REVISE FIRE | | | EASEMENT WORDING ON WATER METER DETAIL TO FIRE/UTILITY | | | EASEMENT; LABEL FIRELINE POINT OF SERVICE VALVES; | | | SUBMIT MEP PLAN (DCDA AREA) FOR REVIEW. | | | | | | -THERE IS A PROPOSED GREASE TRAP THAT IS HALFWAY IN A | | | SIDEWALK AND IN FRONT OF A DOOR. CONSIDER RELOCATING IT | | | OUT OF SIDEWALK. | | | | | | -PROPERTY OWNER WILL BE REQUIRED TO SUBMIT AND RECORD | | | BACKFLOW COVENANT. | | | |
| |