Plan Review Notes For Project Z22050024
Project Number Z22050024
Review Stop PU-CS
Sequence Number 1
Notes
Date Text
2022-07-22 11:41:05PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
  
 FOLLOWUP COMMENTS:
  
 UPON FURTHER REVIEW AT FORMAL ENGINEERING SUBMITTAL,
 PROPOSED WATER SERVICE DESIGN MAY NEED TO TAP OFF
 WATER MAIN IN OKEECHOBEE BLVD.
 RESPONSE: BASED ON EMAIL CORRESPONDENCE, IF THE FIRE
 DEPARTMENT AND PROPERTY OWNER IS OKAY WITH THE
 CONNECTION TO THE PRIVATE 8? DIP FIRE LINE, THEN THE
 UTILITIES DEPARTMENT HAS NO OBJECTION. BASED ON THE
 AS-BUILT PROVIDED, THE 8? MAIN WAS CAPPED AT THE
 IN-LINE BUILDING AND CURRENTLY ONLY SERVICES THE
 FURNITURE STORE AND HYDRANTS.
 FOLLOWUP: UTILITIES DEPARTMENT CONCERN WAS BROUGHT UP
 POSSIBLY AFTER RESPONSE WAS DRAFTED. THIS ISSUE WILL
 NEED TO BE FURTHER EVALUATED AT FORMAL ENGINEERING
 SUBMITTAL IN LIGHT OF ADDITIONAL PROPOSED WATER
 SERVICE. NEW TAPS IN OKEECHOBEE MAY BE NEEDED UPON
 EVALUATION OF CITY OR EOR.
  
 NEW REVIEW COMMENTS:
  
 -L2.0 HAD NOTE ABOUT PAINTING BACKFLOW PREVENTERS.
 CONTAINMENT BACKFLOW ASSEMBLIES CANNOT HAVE SERIAL
 NUMBER NAMEPLATE PAINTED TO WHERE IT BECOMES
 UNREADABLE.
  
  