| 2022-07-22 11:41:05 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | | | | FOLLOWUP COMMENTS: | | | | | | UPON FURTHER REVIEW AT FORMAL ENGINEERING SUBMITTAL, | | | PROPOSED WATER SERVICE DESIGN MAY NEED TO TAP OFF | | | WATER MAIN IN OKEECHOBEE BLVD. | | | RESPONSE: BASED ON EMAIL CORRESPONDENCE, IF THE FIRE | | | DEPARTMENT AND PROPERTY OWNER IS OKAY WITH THE | | | CONNECTION TO THE PRIVATE 8? DIP FIRE LINE, THEN THE | | | UTILITIES DEPARTMENT HAS NO OBJECTION. BASED ON THE | | | AS-BUILT PROVIDED, THE 8? MAIN WAS CAPPED AT THE | | | IN-LINE BUILDING AND CURRENTLY ONLY SERVICES THE | | | FURNITURE STORE AND HYDRANTS. | | | FOLLOWUP: UTILITIES DEPARTMENT CONCERN WAS BROUGHT UP | | | POSSIBLY AFTER RESPONSE WAS DRAFTED. THIS ISSUE WILL | | | NEED TO BE FURTHER EVALUATED AT FORMAL ENGINEERING | | | SUBMITTAL IN LIGHT OF ADDITIONAL PROPOSED WATER | | | SERVICE. NEW TAPS IN OKEECHOBEE MAY BE NEEDED UPON | | | EVALUATION OF CITY OR EOR. | | | | | | NEW REVIEW COMMENTS: | | | | | | -L2.0 HAD NOTE ABOUT PAINTING BACKFLOW PREVENTERS. | | | CONTAINMENT BACKFLOW ASSEMBLIES CANNOT HAVE SERIAL | | | NUMBER NAMEPLATE PAINTED TO WHERE IT BECOMES | | | UNREADABLE. | | | | | | |
| |